EN: Installation Sheet

Description

F-series remote annunciators provide remote LED indicators
and controls for 10-zone F-series control panels. The FSRA10
provides system status LEDs, ten zone active LEDs, and ten
zone trouble LEDs. The FSRA10C provides system status
LEDs, ten zone active and zone trouble LEDs, and common
controls.

This installation sheet applies to the remote annunciator
models listed in Table 1.

Table 1: Compatible models

Model Description

FSRA10

10-zone remote annunciator with system status LEDs
(English overlay)

FSRA10F

10-zone remote annunciator with system status LEDs
(French overlay)

FSRA10C

10-zone remote annunciator with system status LEDs
and common controls (English overlay)

FSRA10CF

10-zone remote annunciator with system status LEDs
and common controls (French overlay)


FSRA10(C) remote annunciators are configured using the jumpers
described in Table 2.

Table 2: Group selection jumper

J2 Description

ON

Selects peripheral group 1

OFF

Selects peripheral group 2

Note: Limit one annunciator per peripheral group

Figures

Figure 1: FSRA10

Figure 2: FSRA10C

Figure 3: Mounting diagram
(1) Compatible electrical box
(2) Mounting

plate

(3) #8 × 1/4 screw

Figure 4: Annunciator rear view

Figure 5: Wiring diagram
(1) From control panel or auxiliary or booster power
(2) From control panel
(3) To next remote module
(4) On: Group 1, Off: Group 2
(5) Remote annunciator key switch (RKEY)

Notes

All wiring is supervised and power-limited.

Use twisted pair cables for data wiring.

AUX power supplied by the control panel can’t exceed 0.5 A. If
more than 0.5 A is required, you must use a power-limited and
regulated 24 VDC auxiliary/booster power supply that is UL/ULC
Listed for fire protective signaling systems.

If powered from an external supply, the supply must be installed
in the same room as the control panel and their 24 VDC
commons (−) wired together.

The RKEY switch wiring is not supervised. The switch must be
located within 3 feet (.91 m) of the annunciator, in the same room,
and enclosed in conduit or is equivalently protected against
mechanical injury.

Installation

1. Attach the mounting plate to the electrical box. See

Figure 3.

2. Configure the remote annunciator for peripheral group 1 or

group 2.

3. Wire the remote annunciator. See Figure 5.

4. Attach the RKEY switch wiring to the annunciator. See

Figure 5.

5. Set the remote annunciator on the mounting plate, and

then secure it with the set screw.