Maintenance, Specifications, Regulatory information – Edwards Signaling SB4U Analog Audible Detector Base Manuel d'utilisation

Page 3: Contact information

Advertising
background image

P/N 3101077 • REV 05 • REB 23JAN13

3 / 6

Table 1: Operating current in mA (RMS)

Voltage

Low dBA

High dBA

16 VDC

17

28

24 VDC

24

41

33 VDC

31

52

16 VFWR

41

48

24 VFWR

51

60

33 VFWR

60

66

VDC = Volts direct current, regulated and filtered
VFWR = Volts full wave rectified

Table 2: Sound level output (dBA) per CAN/ULC-S525

Signal

Voltage (VDC) Low dBA

High dBA

Reverberant room per UL 464 [1]

Temporal

16

71.3

77.2

24

75.0

79.8

33

77.7

81.5

Steady

16

75.8

80.5

24

79.2

84.1

33

82.0

86.0

Reverberant room per UL 268 [2]

Temporal

16

77.3

83.2

24

81.0

85.8

33

83.7

87.5

Steady

16

81.8

86.5

24

85.2

90.1

33

88.0

92.0

[1] For UL 464 applications, low dBA settings are for private mode only
[2] For UL 268 applications, the high setting must be used for
evacuation

Table 3: Audible directional characteristics

Angle (degrees)

Output sound pressure level

90 (reference)

0 dBA

80 and 100

−3 dBA

70 and 110

−6 dBA

Horizontal axis and veritical axis reflect the same pattern

Table 4: Sound pressure level per CAN/ULC-S525

Signal

Voltage

High dBA

Low dBA

Temporal

Reg. 24 VDC

95

91

Reg. 24
VFWR

99

95

Steady

Reg. 24 VDC

93

89

Reg. 24
VFWR

96

92

Maintenance

Do not change the factory-applied finish.

Specifications

Operating voltage (sounder
power)

24 VDC or 24 VFWR

Current

Operating

Supervisory


See Table 1
DC = 1.46 mA, FWR = 2.15 mA

Default settings

Output volume

Output tone


High dBA
Temporal pattern

Sound level output

UL

ULC


See Table 2
See Table 4

Temporal pattern

0.5 s on, 0.5 s off, 0.5 s on, 0.5 s off,
0.5 s on, 1.5 s off, repeat cycle

Compatible detectors

FX-PD, E-PD, FX-PHD, E-PHD,
FX-HD, E-HD, V-PS, V-PHS, V-HRD,
and V-HFD

Compatible electrical boxes

AB4G-SB surface box for audible
base

North American 4 in. square x
2-1/2 in. (64 mm) deep box

Standard European 100 mm² box

Wire size

12 to 18 AWG (0.75 to 2.5mm²)
Sizes 16 and 18 AWG are preferred

Base diameter

6.0 in. (152 mm)

Height from box (including
detector)

2.58 in. (66 mm)

Maximum distance from
ceiling (wall mount)

12 in. (305 mm)

Operating environment

Temperature

Relative humidity


32 to 120°F (0 to 49°C)
0 to 93% noncondensing

Storage temperature range

–4 to 140°F (–20 to 60°C)

Regulatory information

Manufacturer

Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL
34202, USA

Year of
manufacture

The first two digits of the DATE MFG number
(located on the product identification label) are
the year of manufacture.

UL/ULC rating

Regulated 24 DC or 24 FWR

North American
standards

Meets: UL 268, UL 464, CAN/ULC-S525, and
CAN/ULC-S529
Follow: CSA C22.1 and CAN/ULC-S524.

This device is prohibited from being installed in a
dwelling unit as defined in the National Building
Code of Canada
.

Contact information

For contact information, see www.edwardsutcfs.com.