Edwards Signaling 1505 Manuel d'utilisation
Page 2

2 / 4
P/N 3100537 • REV 04 • REB 07FEB13
b. Surface concealed mounting (Figure 6). Measure two points for 1/8 in.
holes drilled 1/2 in. on center equidistant from each marked point. Center
punch the holes and drill 1/8 in. diameter × 1 1/4 in. deep. Install the
concealed mounting plate using the two #10 × 1-1/2 in. screws provided.
Note:
Surface concealed mounting is not recommended for hollow metal,
hollow core, or composite type wood doors.
Align the holes for the concealed mounting plate in the armature base with
the pins on the concealed mounting plate. Secure the armature assembly
with the contact plate adjust screw facing down to the door by tightening
the set screw.
5.
Align the contact plate against the electromagnet. The contact plate must
be centered and lie flat against the magnet to ensure sufficient holding
force. Tighten the contact plate adjusting screw until the plate is firm but not
set. Do not over tighten the contact plate.
6.
Recheck alignment and adjust if necessary.
7.
Adjust the door closer to exert 3 pounds of force when the door is open and
armature and magnet are in contact.
8.
Energize the electromagnet and check operation.
Note:
The unit will not operate without electrical power.
Figure 4: Mounting the armature assembly
Figure 5: Thru-bolt mounting (Cat. Series 1505 shown)
Figure 6: Surface concealed mounting (Cat. Series 1504 shown)
Table 1: Specifications
Cat. no.
Volts
Amps
1504-AQN5
24 VAC 60 Hz
0.015
24 VDC
0.015
120 VAC 60 Hz
0.015
1505-AQN5
24 VAC 60 Hz
0.015
24 VDC
0.015
120 VAC 60 Hz
0.015
Table 2: Dimension chart (in inches (mm))
Y = Dimension of door width
28 30 32 34 36 38 40 42 44 46 48
X = Dimension of do
or jamb to wa
ll
2
26 (660)
28 (711)
29 7/8 (759)
32 (813)
34 (864)
36 (914)
38 (965)
40 (1016)
42 (1067)
43 7/8 (1114)
45 5/8 (1159)
4
26 (660)
28 (711)
29 7/8 (759)
32 (813)
34 (864)
36 (914)
38 (965)
40 (1016)
42 (1067)
43 7/8 (1114)
45 5/8 (1159)
6
25 5/8 (651)
27 5/8 (702)
29 5/8 (752)
31 3/4 (806)
33 3/4 (857)
35 3/4 (908)
37 3/4 (959)
39 3/4 (1010)
41 3/4 (1060)
43 5/8 (1108)
45 3/8 (1153)
8
25 1/4 (641)
27 1/4 (692)
29 1/4 (743)
31 3/8 (797)
33 1/2 (851)
35 1/2 (902)
37 3/8 (949)
39 1/2 (1003)
41 1/2 (1054)
43 3/8 (1102)
45 1/4 (1149)
10
24 5/8 (625)
26 3/4 (679)
28 3/4 (730)
30 7/8 (784)
33 (838)
35 (889)
37 (940)
39 1/8 (994)
41 1/8 (1045)
43 (1092)
44 7/8 (1140)
12
23 3/4 (603)
25 7/8 (657)
28 (711)
30 1/8 (765)
32 1/4 (819)
34 3/8 (873)
36 3/8 (924)
38 1/2 (978)
40 5/8 (1032)
42 1/2 (1080)
44 3/8 (1127)
14
23 3/4 (603)
25 (635)
27 1/4 (692)
29 3/8 (746)
31 1/2 (800)
33 3/4 (857)
35 7/8 (911)
38 (965)
40 (1016)
42 (1067)
43 7/8 (1114)
16
21 3/4 (552)
24 (610)
26 1/4 (667)
28 1/2 (724)
30 3/4 (781)
33 (838)
35 1/8 (892)
37 1/4 (946)
39 3/8 (1000)
41 3/8 (1051)
43 3/8 (1102)
18
20 (508)
22 1/2 (572)
25 (635)
27 3/8 (695)
29 3/4 (756)
32 (813)
34 1/4 (870)
36 1/2 (927)
38 5/8 (981)
40 5/8 (1032)
42 1/2 (1080)
20
18 1/4 (463)
21 (533)
23 1/2 (597)
26 (660)
28 1/2 (724)
30 7/8 (784)
33 1/8 (841)
35 3/8 (899)
37 5/8 (956)
39 5/8 (1006)
41 5/8 (1057)
22
18 3/4 (476)
21 5/8 (549)
24 3/8 (619)
27 (686)
29 3/8 (746)
31 3/4 (806)
34 1/8 (867)
36 1/2 (927)
38 5/8 (981)
40 3/4 (1035)
24
22 1/2 (572)
25 1/2 (648)
28 1/8 (714)
30 5/8 (778)
33 1/8 (841)
35 5/8 (905)
37 7/8 (962)
40 (1016)
26
Do not install outlet box if
26 1/4 (667)
29 (737)
31 5/8 (803)
34 1/4 (870)
36 1/2 (927)
38 5/8 (981)
28
Dimensions X and Y intersect in this blank area.
29 3/4 (756)
32 1/2 (826)
34 7/8 (886)
37 1/8 (943)
30
The armature and electromagnet cannot be aligned.
27 3/4 (705)
30 5/8 (778)
33 (838)
35 3/8 (899)
32
31 3/8 (797)
33 7/8 (860)