MaxPower Corp Gamatronic Power+ M50 Manuel d'utilisation
Page 174

Gamatronic Electronic Industries Ltd.
158
POWER+ 3x208 V, User Guide, Release 2.3
Dimensions (U.S. measurements)
UPS type
10 kVA 20 kVA 30 kVA 40 kVA 50 kVA 60 kVA 70 kVA 80 kVA 90 kVA 100 kVA
Height
(in)
27.2 31.1 34.6 38.2 42.1 49.6 53.2 56.7 60.6 64.6
Width (in)
23.6
Depth (in)
27.2
39.0
Weight
(lbs) 223 258 291 326 359 428 463 496 531 564
Dimensions (metric measurements)
UPS type
10 kVA 20 kVA 30 kVA 40 kVA 50 kVA 60 kVA 70 kVA 80 kVA 90 kVA 100 kVA
Height
(cm) 69 79 88 97 107 126 135 144 154 164
Width (cm)
60
Depth (cm)
69
99
Weight
(kg) 101 117 132 148 163 194 210 225 241 256
Acoustic Noise
Noise (dBA)
with
half
load
48 52 53 54 55 55.8
56.4
57 57.5
58
Noise (dBA)
with
full
load 51 54 55 57 58 58.8
59.4
60 60.5
61
All specifications are subject to change without notice.
SYSTEM CONTROLLER – TECHNICAL DATA
Micro Controller core
16 bit
Display
4 × 40 characters LCD with backlight
Other indicators
8 LEDs, buzzer
Analog input channels
4 input dry contacts (N.C.)
Real Time Clock (RTC)
Yes, with backup
Power meter
kVA, kW, PF
Volt-free outputs (dry contacts)
6 outputs, rated 50 V / 1 A
Communication
TCP/IP, GPRS/SMS wireless communications
(optional)
Communications with system modules
Serial, isolated
Events log
255 events
System operation without controller
Unchanged
On-screen parameters
Load bar-graph, 3-phase voltages,
3-phase currents, battery voltage,
status of each UPS module
static-switch parameters and status
battery sensor temperature
Alarms
Ac failure, dc failure, UPS module(s) failure,
load on bypass, battery test failure,
over/under temperature, overload
(contacts rated max. 48 V 1 A)
RTC operation without power
2 weeks
Power requirements
3 × 208 Vac / ±216 Vdc 15 W