1 setting upss, 2 testing dry output relays, Setting upss – MaxPower Corp Gamatronic Power+ M50 Manuel d'utilisation
Page 128: Testing dry output relays, Figure 219: setup menu, Figure 220: service menu, Figure 221: set upss, Figure 222: service menu

Gamatronic Electronic Industries Ltd.
112
POWER+ 3x208 V, User Guide, Release 2.3
2. Select
Service:
[Main Menu > SETUP > (password) > Ent]
1> Alarm set 5> Time 9> Silicon
2> Module conf. 6> Site
3> Battery 7> Password #1
4> Charge 8> Service
Figure 219: Setup menu
8.12.1
Setting UPSs
1. Select
UPSs:
[Main Menu > SETUP > (password) > Ent > Service]
1> ------ 4> DryOut Test 7> --------
2> UPSs 5> Configure 8> Powr.Calib
3> ------- 6> En/Dis shar 9> SC2012..
Select, then Enter
Figure 220: Service menu
2.
Use the arrow keys to set UPSs, and press Esc when finished:
[Main Menu > SETUP > (password) > Ent > Service > UPSs]
1234
++++
SET UPSs (UP= ON<+>, DOWN= OFF<->)
Enter = Execute Esc= Go back
Figure 221: Set UPSs
8.12.2
Testing Dry Output Relays
1. Select
DryOut Test:
[Main Menu > SETUP > (password) > Ent > Service]
1> ------ 4> DryOut Test 7> --------
2> UPSs 5> Configure 8> Powr.Calib
3> ------- 6> En/Dis shar 9> SC2012..
Select, then Enter
Figure 222: Service menu