3 setting module/s voltage, 4 update voltage/frequency/phase, Setting module/s voltage – MaxPower Corp Gamatronic Power+ M50 Manuel d'utilisation
Page 105: Update voltage/frequency/phase, Figure 149: module config. setup menu, Figure 150: setting the module/s voltage, Figure 151: module config. setup menu

Gamatronic Electronic Industries Ltd.
POWER+ 3x208 V, User Guide, Release 2.3
89
8.9.3
Setting Module/s Voltage
1. Select
Module/s voltage:
[Main Menu > SETUP > (password) > Module conf.]
1. Num of phase 5.Output Adjust
2. Module/s frequency 6.Frequency Limits
3. Module/s voltage 7.DC Calibration
4. Update Vo/Fr/ph 8.AC Calibration
Figure 149: Module Config. setup menu
2. Use
the
▲▼arrow keys to set the module/s voltage, press Ent, and then Esc:
[Main Menu > SETUP > (password) > Module conf. > Module/s voltage]
Module/s voltage 4: 118V
1: 110V 5: 120V
2: 113V 6: 125V
3: 115V (selected) 5: 130V
Figure 150: Setting the Module/s voltage
8.9.4
Update Voltage/Frequency/Phase
1. Select Update Vo/Fr/ph:
[Main Menu > SETUP > (password) > Module conf.]
1. Num of phase 5.Output Adjust
2. Module/s frequency 6.Frequency Limits
3. Module/s voltage 7.DC Calibration
4. Update Vo/Fr/ph 8.AC Calibration
Figure 151: Module Config. setup menu
2. Press
Ent to update, and then Esc:
[Main Menu > SETUP > (password) > Module conf. > Update Vo/Fr/ph]
Nominal Voltage & Frequency
have been sent to all modules.
Please verify all modules were updated!
Exit this mode by pressing Esc.
Figure 152: Updating the Module/s voltage/frequency/phase