2 second general screen, Second general screen, Figure 289: general (screen 2) – MaxPower Corp Gamatronic Power+ M50 Manuel d'utilisation
Page 149

Gamatronic Electronic Industries Ltd.
POWER+ 3x208 V, User Guide, Release 2.3
133
8.15.9.2
Second General Screen
From the screen shown in the previous section, press
► to view screen 2:
[3-second Esc > GENERAL >
►]
CURRSHARE RST: DIS #OF PHASE: AUTO
REV : SC25230909 LVD BY AC FAIL: DIS
MAINT: 2010.05.12 TEMP. SENSOR: DIS
SITE : 000001 CURR. SENSOR: DIS
Figure 289: General (Screen 2)
A description of the various system parameters shown in screen 2 are listed below.
a.
CURRSHARE RST: displays the status of the current sharing—either enabled or
disabled (EN or DIS).
b.
#OF PHASE: FORCE 3 for 3 phase output, FORCE 1 for single phase output or
AUTO when the mode is defined by DIP SWITCH of the modules.
c.
REV: revision of the system controller (SC) software.
d.
LVD BY AC FAIL: DIS (disabled) or EN (enabled). This function, if enabled, performs
system shutdown after 3 hours of ac failure to prevent deep battery discharge by low
current. For most applications, the function must be disabled.
e.
MAINT: YEAR.MONTH.DAY: date of last maintenance.
f.
TEMP. SENSOR: DIS or EN. External temperature sensor is disabled/ enabled. In
most applications, it must be disabled.
g.
SITE: the site identification number is used in network applications.
h.
CURR.SENSOR: DIS or EN. Optional battery current sensor is disabled/ enabled. In
most applications, it must be disabled.