Figure 263: network menu, Figure 264: network menu, Figure 265: setting the snmp no comm factor – MaxPower Corp Gamatronic Power+ M50 Manuel d'utilisation
Page 139: Figure 266: sc2012 menu

Gamatronic Electronic Industries Ltd.
POWER+ 3x208 V, User Guide, Release 2.3
123
11. Select
Store:
[Main Menu > SETUP > (password) > Ent > Service > SC2012 > Network]
1> Set IP ADDRESS 157.211.000.253
2> Set GATEWAY 157.211.000.251
3> Set MASK 255.255.255.000
4> Store 5> SNMP factor Select:1
Figure 263: Network menu
Entered information is stored.
12. Select
SNMP factor:
[Main Menu > SETUP > (password) > Ent > Service > SC2012 > Network]
1> Set IP ADDRESS 157.211.000.253
2> Set GATEWAY 157.211.000.251
3> Set MASK 255.255.255.000
4> Store 5> SNMP factor Select:1
Figure 264: Network menu
13. Use the arrows keys to set the SNMP NO COMM Factor, press Ent and then Esc:
[Main Menu > SETUP > (password) > Ent > Service > SC2012 > Network > SNMP factor]
Set SNMP NO COMM Factor Value
(10 - 99)
50
Figure 265: Setting the SNMP NO COMM factor
14. Select
Reset MBX:
[Main Menu > SETUP > (password) > Ent > Service > SC2012 > Reset MBX]
1> Restart controller 3> Network…
2> Factory settings 4> Reset MBX
Your selection: 1 5> --------------
Enter if you are sure (else press Esc.!)
Figure 266: SC2012 menu
The MBX is reset.