Installation & Servicing Instructions Rinnai E-Series
72
15
Blocks and Errors
15.1 Error indication (short reference)
A detected error is indicated on the display by means of blocking or error messages. A
distinction should be made between these two messages due to the fact that blocking
can be of a temporary nature, however, error messages are fi xed lockings. The control
will try its utmost to prevent locking and will temporarily switch off the unit by blocking
it. Hereunder is a list of some messages.
Blocks
with a number in the last 2 positions.
Block
01:
External safety contact cut off
Block
60:
Incorrect parameter setting of the minimum or maximum power.
Block
67:
A
T has been detected between fl ow and return sensor whereas the burner is not in operation.
After
the
T has disappeared the block will clear.
Block
85:
The control has not detected a water fl ow. The venting cycle is started.
If during this cycle water fl ow is detected, the venting cycle is ended and the burner is released.
Error
with a number in the last two positions.
Error
00:
Poor
fl ame-forming
Error
02:
no
fl ame-forming
Error 04: adjustment or error for voltage interruption
Error
05:
adjustment
Error 12: high limit stat
Error
18:
maximum
fl ow temperature exceeded
Error 19: maximum return temperature exceeded
Error 28: number of revolutions not reported back from fan
Error 69: no or incorrect display
FUSE:
24V fuse defective