2 clearances from boiler – Rinnai E110CP Manuel d'utilisation
Page 16

Installation & Servicing Instructions Rinnai E-Series
16
clearances to the boiler
table 3
service clearances to the boiler
figure 4
wall
ceiling
For closet installation: clearance is 1” / 25mm from the front.
Low Loss Header
Clearances to combustible and non-Combustible is 0 inch for sides, top, front and fl oor/ground
The recommended service clearance to the bottom of the low loss header is 12 inches.
2"
50
Min. 10" /
250mm
15.7"
400
24"
600
5.3.2
Clearances from boiler
Minimum required clearances
to combustibles
Minimum required clearances
to non-combustibles
Recommended
service clearances
All types
All types
All types
inch / mm
inch / mm
inch / mm
Top of boiler
2" / 50
2" / 50
10" / 250
Back of boiler
0"
0"
0
Front of boiler
6" / 150
6" / 150
24" / 600
Left side of boiler
2" / 50
2" / 50
2" / 50
Right side of boiler
2" / 50
2" / 50
2" / 50
Floor / Ground to
bottom of boiler
12" / 300
12" / 300
30" / 762
Floor/ Ground to
bottom Low loss
header
0"
0"
12" / 300
Vent 0"
0"
0"
2"
50