1 reset service interval counter, 4 warranty – Rinnai E110CP Manuel d'utilisation
Page 69

Installation & Servicing Instructions Rinnai E-Series
69
Visual inspection of the fl ame (2 and 4 year maintenance)
The burner must fl ame evenly over the entire surface when operating correctly. The
fl ame must burn with a clear, blue, stable fl ame.
Check the fl ame through the inspection glass in the ignition probe (fi g. 38).
The fl ame pattern should be as shown in the fi gures below.
Further checks:
- Inspect the pressure relief valve
- Clean the water fi lter in the return pipe
- Check the pH of the water or glycol/water mixture.
The combustion must be checked and adjusted if required at both the 2
year/2000 hour and 4 year/4000 hour service intervals with a properly working
combustion analyzer.
Verify proper operation after servicing. Always reset the service interval counter after
full maintenance interval (every 4 years or 4000 hours of operation).
13.3.1
Reset service interval counter
At 4000 hours of use, “SERVICE” will scroll across the display. “Good” will display
as well alternatively.
To reset the 4000 hour service notifi cation:
- Enter the 1st Tier Settings: 123 Code
- Briefl y press “Mode” again until the Service Chapter is displayed (SERV)
- Hold the “Store” button until SERV fl ashes once—the service notifi cation will no
longer show during normal operation and the countdown to service will reset to
4000.
13.4 Warranty
For warranty conditions refer to the warranty card supplied with the boiler.
SATISFACTORY
Ignition probe
blue
fl ame
UNSATISFACTORY
Ignition probe
yellow
fl ame
Inspection glass
figure 39
NOTICE
i
Water filter
figure 40