Installation & Servicing Instructions Rinnai E-Series

38

See Boiler Applications manual for additional venting information.

Terminals should be positioned as to avoid products of combustion entering
openings into buildings or other vents.

Maintain 12” of clearance above the highest anticipated snow level or grade
or, whichever is greater. Please refer to your local codes for the snow level in
your area.

The termination shall be at least 4 feet (1,220 mm) for the US and 6 feet (1,830
mm) for Canada distance from electric meters, gas meters, regulators and
relief equipment. (for room air application only)

Horizontal vent systems should always be installed sloping towards the
boiler (min. 21 mm/m, 1/4”/ feet), in order to avoid condensate retaining in the
vent system. With the condensate running back to the boiler the risk of ice
forming at the terminal is reduced.

The whole route of the vent system must be installed upwards, never
downwards, completely nor partly.

Place pipe supports every 4 feet (1219 mm) of horizontal run, beginning with
the support near the boiler to prevent movement in fi ttings and allow boiler
to be free from any strain or weight on boiler or fi ttings.

The terminal should be located where dispersal of combustion products is
not impeded and with due regard for the damage or discoloration that might
occur to building products in the vicinity (see fi g 15 and 16).

In certain weather conditions condensation may also accumulate on the
outside of the air inlet pipe. Such conditions must be considered and where
necessary insulation of the inlet pipe may be required.
In cold and/or humid weather water vapor may condense on leaving the vent
terminal. The effect of such ‘water condensation’ must be considered.

The terminal must be located in a place not likely to cause a nuisance.

Use the Instructions of the Rinnai venting system for installation and service.

Cellular or Foam core PVC is not permitted for use with the boiler.

NOTICE

i

!

CAUTION

!

CAUTION

NOTICE

i

NOTICE

i

NOTICE

i

NOTICE

i

Approval codes for installation of venting system

table 7

Item Description

Flue Material

United States

PVC Schedule 40

ANSI/ASTM D1785

PVC - DWV

ANSI/ASTM D2665

CPVC Schedule 40 ANSI/ASTM F441
PVC

ANSI/ASTM D2564

CPVC

ANSI/ASTM F493

Item Description

Flue Material

Manufacturer

Approval code
US/CAN

Flue system

Stainless steel vent
systems

Stainless Steel

Ubbink

Rolux Condensing
Vent System

Plastic Vent System

PPS

Ubbink

Rolux Condensing
Vent System

Plastic Vent System

PVC/CPVC

IPEX

ULC S636

System 636

Approval Codes for Installation

Canada

Plastic Vent and/or air
pipes and fittings

ULC S636

Plastic Pipe cement and
primer

Stainless steel vent
systems

Stainless Steel

Simpson Dura-Vent

FastNSeal Flex
FastNSeal

UL1738 Flexible liner
UL1738 Concentric

twin pipe

Saf-T Vent SC
Saf-T Vent EZ Seal

Stainless steel vent
systems

Stainless Steel

Heat Fab

UL1738 Concentric

twin pipe

NOTICE

i

NOTICE

i