Warning – Napoleon Fireplaces Grandville 36 - BGD36 Manuel d'utilisation
Page 37

37
W415-0773 / F / 08.26.13
EN
Combustion protrusions such as mantels and shelves may occur at or after a minimum distance of 2" (51mm)
away from the side of the appliance. Thereafter, the depth of any protrusions must be equal to or less than the
distance from the side of the appliance up to a depth of 6" (152mm), after which no greater clearance than 6"
(152mm) is required. This can be considered a side wall with no length boundary.
6.2.1 MINIMUM FRAMING DIMENSIONS
36 1/2"
927mm
35 3/4"
908mm
3" 76mm
5 1/2" 140mm
14 1/2"
368mm
39" 991mm
(REAR EXIT)
48 3/8" 1229mm
(TOP EXIT)
3 1/2"
89mm
MAX
1 1/2"
38mm
MAX
14"
356mm
MINIMUM
GAS
INLET
LOCATION
FINISHING
MATERIAL
ENCLOSURE
TOP
TOP EXIT INSTALLATION
SHOWN
OUTSIDE
CHASE
INSIDE
CHASE
PROTRUSION
SIDE
WALL
14 1/2"
368mm
37 3/4" 959mm
37 3/4" 959mm
14 1/2"
368mm
2" 51mm
2" 51mm
4" 102mm
4" 102mm
6" 152mm
34 3/4"
882mm
49 1/8"
1247mm
35 1/2"
901mm
FOR TOP EXIT APPLICATIONS: DO NOT BUILD INTO THIS AREA. IT MUST BE LEFT CLEAR TO
PROVIDE ADEQUATE CLEARANCE FOR THE VENT. IN THIS 14" (356MM) WIDE AREA CENTRED
ALONG THE FRONT OF THE APPLIANCE, NO COMBUSTIBLES ARE ALLOWED.
!
WARNING
* BGD36 HORIZONTAL VENT SECTIONS:
A minimum of 1" (25mm) at the bottom and sides and 2" (51mm)
at the top of the vent pipe on all horizontal runs to combustibles is required. Use fi restop spacer W010-1774
(supplied).
* BGD36 VERTICAL VENT SECTIONS:
A minimum of 1" (25mm) all around the vent pipe on all vertical runs
to combustibles is required except for clearances in appliance enclosures. See "MINIMUM ENCLOSURE
CLEARANCES" section. Use fi restop spacer W500-0096 (not supplied).