Installation of sti-1215 stopper, Dome for strobe flush mount

Safety Technology International, Inc.
2306 Airport Road • Waterford, Michigan 48327-1209
Phone: 248-673-9898 • Fax: 248-673-1246
Toll Free: 800-888-4784 • E-mail: [email protected]
Web: www.sti-usa.com
Safety Technology International (Europe) Ltd.
Unit 49G Pipers Road • Park Farm Industrial Estate • Redditch
Worcestershire • B98 0HU • England • Tel: 44 (0) 1527 520 999
Fax: 44 (0) 1527 501 999 • Freephone: 0800 085 1678 (UK only)
E-mail: [email protected] • Web: www.sti-europe.com
INSTALLATION OF STI-1215 STOPPER
®
DOME FOR HORN/SPEAKER/STROBE FLUSH MOUNT
AND STI-1225 STOPPER
®
DOME FOR STROBE FLUSH MOUNT
All specifications and information shown were current as of publication and are subject to change without notice.
INSTALLATION NOTES
1. To minimize strobe light loss, regardless of the type of horn/strobe appliance used, the clear
section (not the section containing the cutout slots) must be centered over the strobe light lens.
Failure to follow these instructions may lead to light loss transmission.
2. Stopper Dome must be installed to comply with applicable NEC, NFPA and local codes.
3. Stopper Dome may be installed outdoors when appliance carries an outdoor rating.
Electronic warranty form at www.sti-usa.com/wc14
1225-15IS AUG2009
CLEANING INSTRUCTIONS
Rinse with water to remove abrasive dust and dirt. Wash with soap or mild detergent, using a soft
cloth (do not scrub). Rinse once more then dry with a soft cloth or chamois. To remove grease or wet
paint, rub gently with a cloth wetted with naphtha. Then wash and rinse. DO NOT USE RAZOR BLADES.
INSTALLATION INSTRUCTIONS - REFER TO EXPLODED VIEW
1. Using cover as a template, place against mounting surface at proper location according to NFPA 72.
2. Mark and drill (6) holes 3/16 in. (4.7mm) diameter, 1 1/4 in. (32mm) deep.
3. Insert the (6) anchors into the wall.
4. Install horn/strobe appliance.
5. Install cover with washers and screws.
6. Test appliance according to appliance manufacturer’s instructions.
All specifications and information shown were current as of publication, and are subject to change without notice.
19018 ANCHOR
(6) PROVIDED
01225 COVER
(STROBE ONLY)
19049 WASHER
(6) PROVIDED
19028 SCREW
#8 x 1 1/2 in.
(6) PROVIDED
EXISTING WARNING
APPLIANCE
DRILL (6)
3/16 in.(4.7mm)
DIA. HOLES
IF ADDED PROTECTION
IS NEEDED DUE TO
ENVIROMENTAL CONDITIONS
INSERT GASKET IN GROOVE
ON UNDERSIDE OF COVER
(1) PROVIDED
01215 COVER
(HORN/STROBE)
TYPICAL CEILING MOUNT
APPLICATION
2.87 in.(73mm)
7.37 in.(187mm)
GASKET
EXISTING WARNING
APPLIACE
PRODUCT DIMENSIONS
REMARQUES SUR L’INSTALLATION
1. Afin de minimiser la perte de lumière stroboscopique, quel que soit le type d’alarme sonore/de stroboscope utilisé, la
section dégagée (et NON la section contenant les fentes de découpe), doit être centrée sur l’objectif stroboscopique. Le
fait d’omettre ces instructions risque d’entraîner la perte de diffusion de la lumière.
2. Le dôme Stopper doit être installé de sorte à être conforme avec les normes NEC, NFPA applicables et les codes locaux.
3. Il est possible d’installer un dôme Stopper à l’extérieur lorsque l’appareil est homologué pour utilisation à l’extérieur.