Installation – Garland SR16 Manuel d'utilisation

Page 6

Advertising
background image

Part # 1382684 Rev. 1 (02/11/11)

Page 6

INSTALLATION

Clearances

Models (M, MS, MST)(SRC, SR16) are for installation in non-

combustible locations only with zero (0”) sides and rear

clearance.

NOTE: Adequate clearance must be provided for servicing

and proper operation.

Location

Counter salamanders should be installed on a firm, smooth

and level base designed to withstand the weight of the fully

laden appliance. Any openings in the wall behind or beside

the appliance must be sealed.

Installation Instructions for

Range Mount Salamander

~

1

"X"

"X"

2

8

4

3

6
7

5

GA

RLA

ND

1. Remove the front panel (5) by removing two (2), sheet

metal screws from the underside of the salamander.

2. With the back panel, (4), still attached to the uprights

(2&3) drop the uprights into the rectangular openings at

the rear of the range (1).

3. Fasten the uprights, (2 & 3) to the range with four, (4),

5/16” x 18 bolts and flat washers. (6&7)

4. If the range is in a battery line-up, fasten units together

at the hole marked “X” with 1/4” x 20 bolts, nuts and

washers.

5. Reattach the front panel (5) to the salamander with sheet

metal screws previously removed.

Wall Mounted Salamanders

1. Each gas appliance must be located with respect to

building construction and other equipment so as to

permit access to the appliance, Such access and clearance

may be necessary for servicing and cleaning.

2. Salamanders intended for wall mounting are shipped

with the mounting kit already attached.

3. Provisions for gas connections, bottom or rear should be

taken into consideration.

Statutory Regulations

When checking gas pressure be sure that all other

equipment on the same gas line is on. A pressure regulator is

supplied as standard equipment with Garland salamanders.

Installation must conform to the National Fuel Gas Code ANSI

Z223.1 or latest edition and/or local code to assure safe and

efficient operation.

In Canada, the installation must comply with

CAN/CGA-B149.1 Natural Gas Installation Code or CAN/CGA-

B149.2 Propane Gas Installation Code, and local codes where

applicable.

NOTE: The appliance must be isolated from the gas supply

piping system by closing it individual manual shut-off (not

supplied by the manufacturer) during any testing of the gas

supply piping system at test pressures equal to or less than

1/2 PSIG (3.45 kPa).