CCI Thermal Technologies CX1 - ProVector Explosion-Proof Convection Heater Manuel d'utilisation
Cx1 provector, Series, Owner’s manual

OWNER’S MANUAL
CX1 ProVector
®
Series
Electric Convection Air Heaters for Hazardous Locations
APPROVED LOCATIONS
Electric convection air heaters are cULus listed for
the following hazardous locations:
(without built-in thermostat)
Class I, Div. 1 & 2, Groups A, B, C & D
Class I, Zones 1 & 2, Groups IIA, IIB, IIC
Temperature Code T2A 536°F (280°C),
T3 392°F (200°C)
(with built-in thermostat)
Class I, Div. 1 & 2, Groups A, B, C & D
Class I, Zones 1 & 2, Groups IIA & IIB, IIC
Temperature Code T2A 536°F (280°C), T3 392°F (200°C)
For details of hazardous locations with potential for
explosion, refer to the Canadian Electrical Code,
Part 1, Section 18 or National Electrical Code
Articles 500 - 516.
Ruffneck
TM
and ProVector
®
are registered trademarks of CCI Thermal Technologies Inc.
Copyright © 2013. All rights reserved.
Pt. No. 6348.Rev.16.01
Printed in Canada
Issue Date: February 2013
– 1 –
This manual covers installation, maintenance, repair and parts.
WARNING!
READ ALL IMPORTANT NOTICES ON PAGE 3.
PLEASE ADHERE TO INSTRUCTIONS PUBLISHED IN THIS MANUAL.
Failure to do so may be dangerous and may void certain provisions of your warranty.
CX1 - 120 1 60 - 012 - T2A - IIB - T
MODEL CODING
KILOWATTS
0075 - 0.75kW 018 - 1.8kW
036 - 3.6kW
0083 - 0.83kW 0226 - 2.26kW 0476 - 4.76kW
009 - 0.90kW 025 - 2.5kW
048 - 4.8kW
0113 - 1.13kW 0269 - 2.69kW 0528 - 5.28kW
012 - 1.2kW
0301 - 3.01kW 0568 - 5.68kW
0125 - 1.25kW 0333 - 3.33kW 076 - 7.6kW
0135 - 1.35kW 0359 - 3.59kW
MODEL SERIES
VOLTAGE
120V
208V
240V
277V
380V
400V
415V
480V
600V
PHASE
UNITS IN
SINGLE PHASE
ONLY
FREQUENCY
50 or 60 HERTZ
T-CODE
T2A - 536ºF (280ºC)
T3 - 392ºF (200ºC)
HAZARDOUS
LOCATION
IIB
IIC
BUILT-IN T'STAT
ADD 'T' FOR
T'STAT