Appendix i: input wiring requirements – Tweco 100XL Plus PAK Master Manuel d'utilisation
Page 45

Manual 0-2811
A-1
APPENDIX
APPENDIX I: INPUT WIRING REQUIREMENTS
Input
Power Input
Current Input
Suggested Sizes (See Notes)
Voltage
Freq.
1-Ph
3-Ph
1-Ph
3-Ph
Fuse (Amps)
Wire (AWG)
Wire (Canada)
(Volts)
(Hz)
(kVA)
(kVA)
(Amps)
(Amps)
1-Ph
3-Ph
1-Ph
3-Ph
1-Ph
3-Ph
208
50/60
18.9
17.3
91
48
100
60
2
4
2
4
230
50/60
18.9
17.3
82
43.5
90
50
2
6
2
6
240
50/60
19
17.5
79
42
80
50
2
6
2
6
380
50/60
21.2
19.1
55.9
29
70
35
4
8
4
8
415
50/60
21.2
19.4
51.2
27
60
35
6
8
6
8
460
50/60
21.2
20.4
46
25.6
50
30
6
8
6
8
575
Requires Transformer Module
Line Voltages with Suggested Circuit Protection and Wire Sizes
Based on National Electric Code and Canadian Electrical Code
NOTES
The table above is based on the following output current & voltage: 140VDC @ 80A
Refer to Local and National Codes or local authority having jurisdiction for proper wiring requirements.
Cable size is de-rated based on the Duty Cycle of the equipment.
The suggested sizes are based on flexible power cable with power plug installations. For hard-wired installations
refer to local or national codes.
Cable conductor temperature used is 167° F (75° C).
An energy limiting fuse UL Class RK-1 (examples: BUSS LPS/LPN-RK or Gould-Shawmut AZK-A6K) should be
used to minimize damage to Plasma Cutting, Welding or power distribution equipment.
NEVER
use replaceable element fuses like UL Class H, or "one-time" fuses like UL Class K5.
Flexible cable must have an outside diameter of 0.69 inches (17.5 mm) or greater.