Rockwell Automation 1769-PB4 Compact I/O Expansion Power Supplies Manuel d'utilisation
Page 32

32 Compact I/O Expansion Power Supplies
Publication 1769-IN028B-EN-P - October 2008
Vibration
IEC 60068-2-6 (Test
Fc, Operating)
5 g @ 10…500 Hz
Operating shock
IEC 60068-2-27
(Test Ea,
Unpackaged Shock)
DIN rail mount: 20 g; Panel Mount 30 g
Nonoperating
shock
IEC 60068-2-27
(Test Ea,
Unpackaged Shock)
DIN rail mount: 30 g; Panel Mount 40 g
Emissions
CISPR 11
Group 1, Class A
ESD immunity
IEC61000-4-2
4 kV contact, 8 kV air discharges
Radiated RF
immunity
IEC61000-4-3
10V/m with 1 kHz
sine-wave 80%
AM from 80…2000
MHz
3V/m with 1 kHz
sine-wave 80%
AM from
2000…2700 MHz
10V/m with 200 Hz
50% Pulse 100%
AM at 900 MHz
10V/m with 200 Hz
50% Pulse 100%
AM at 1890 MHz
10V/m with 1 kHz
sine-wave 80%AM
from 80…2000
MHz
10V/m with 200 Hz
50% Pulse
100%AM at 900
MHz
10V/m with 1 kHz
sine-wave 80%
AM from 80…2000
MHz
3V/m with 1 kHz
sine-wave 80%
AM from
2000…2700 MHz
10V/m with 200 Hz
50% Pulse 100%
AM at 900 MHz
10V/m with 200 Hz
50% Pulse 100%
AM at 1890 MHz
10V/m with 1 kHz
sine-wave 80%AM
from 80…2000
MHz
10V/m with 200 Hz
50% Pulse
100%AM at 900
MHz
EFT/B immunity
IEC 61000-4-4
+2 kV at 5 kHz on
AC power ports
±2 kV at 5 kHz on
24V DC PWR OUT
ports
+2 kV at 5 kHz on
DC power ports
+2 kV at 5 kHz on
AC power ports
+2 kV at 5 kHz on
DC power ports
Surge transient
immunity
IEC61000-4-5
±2 kV line-line (DM)
and ±4 kV line-earth
(CM) on AC power
ports
±500V line-line
(DM) and ±500V
line-earth (CM) on
24V DC PWR OUT
ports
±500V line-line (DM)
and ±500V
line-earth (CM) on
DC power ports
±2 kV line-line (DM)
and ±4 kV line-earth
(CM) on AC power
ports
±500V line-line (DM)
and ±500V
line-earth (CM) on
DC power ports
1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4 - Environmental Specifications
Attribute
1769-PA2
1769-PB2
1769-PA4
1769-PB4