Figure 7—option de câblage ex d, Figure 8— option de câblage ex e – Det-Tronics X9800 IR Flame Detector Manuel d'utilisation
Page 11

9
95-6554
11.1
B2176
TABLEAU D'ALARME INCENDIE
DÉTECTEUR X9800
ALARME
24 Vcc
+
–
NOTES SUR LE CABLAGE:
1 EN FONCTIONNEMENT NORMAL ET EN CAS D'ABSENCE DE DÉFAUT, LE RELAIS
DÉRANGEMENT EST EXCITÉ ET SES CONTACTS SONT NORMALEMENT FERMÉS.
2 LE RELAIS D'ALARME FEU EST NORMALEMENT DÉSACTIVÉ EN CAS D'ABSENCE DE DÉFAUT.
3 DES COMMUTATEURS DE TEST
oi INDIVIDUELS (OU BIEN UN SÉLECTEUR DE DÉTECTEUR
AVEC UN COMMUTATEUR D'ACTIVATION) PEUVENT ÊTRE INSTALLÉS SUR LE TABLEAU INCENDIE.
LES COMMUTATEURS DE TEST NE SONT PAS FOURNIS.
4 SE RÉFÉRER AU CHAPITRE "CARACTÉRISTIQUES" POUR LES VALEURS DE RÉSISTANCE
DE FIN DE LIGNE. SE RÉFÉRER AU CHAPITRE "RÉSISTANCES FIN DE LIGNE"
POUR LES DÉTAILS SUR L'INSTALLATION.
FIN DE
LIGNE4
TEST
oi3
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
COMMUN
FEU2
COMMUN
FEU
N.O. FEU2
N.O. FEU
N.F. FEU2
N.F. FEU
COMMUN
DÉRANGEMENT
COMMUN
DÉRANGEMENT
N.O.
DÉRANGEMENT
N.O.
DÉRANGEMENT
24 Vcc +
24 Vcc +
24 Vcc –
24 Vcc –
24 Vcc –
29
28
27
26
25
24
23
22
21
LIBRE
LIBRE
RS-485 A
RS-485 B
Oi MANUEL
4-20 mA +
4-20 mA –
4-20 mA + REF
4-20 mA – REF
COMMUN AUXILIAIRE
N.O. AUXILIAIRE
N.F. AUXILIAIRE
Figure 7—Option de Câblage Ex d
B2177
TABLEAU D'ALARME INCENDIE
DÉTECTEUR X9800
ALARME
ALARME
24 Vcc
+
–
NOTES SUR LE CABLAGE:
1 EN FONCTIONNEMENT NORMAL ET EN CAS D'ABSENCE DE DÉFAUT, LE RELAIS DÉRANGEMENT
EST EXCITÉ ET SES CONTACTS SONT NORMALEMENT FERMÉS.
2 LE RELAIS D'ALARME FEU EST NORMALEMENT DÉSACTIVÉ EN CAS D'ABSENCE DE DÉFAUT.
3 DES COMMUTATEURS DE TEST
oi INDIVIDUELS (OU BIEN UN SÉLECTEUR DE DÉTECTEUR
AVEC UN COMMUTATEUR D'ACTIVATION) PEUVENT ÊTRE INSTALLÉS SUR LE TABLEAU INCENDIE.
LES COMMUTATEURS DE TEST NE SONT PAS FOURNIS.
4 RÉSISTANCE DE FIN DE LIGNE FOURNIE AVEC LE TABLEAU D'ALARME INCENDIE.
RÉSISTANCE
DE FIN
DE LIGNE4
TEST oi3
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
COMMUN
FEU2
COMMUN
FEU
N.O. FEU2
N.O. FEU
N.F. FEU2
N.C. VEU
COMMUN
DÉRANGEMENT 1
COM
FAULT
N.O.
DÉRANGEMENT1
N.O.
DÉRANGEMENT
24 Vcc +
24 Vcc +
24 Vcc –
24 Vcc –
24 Vcc –
29
28
27
26
25
24
23
22
21
LIBRE
LIBRE
RS-485 A
RS-485 B
MAN
Oi
4-20 mA +
4-20 mA –
4-20 mA + REF
4-20 mA – REF
COMMUN
AUXILIAIRE
N.O. AUXILIAIRE
N.F. AUXILIAIRE
Figure 8— Option de Câblage Ex e