Samlex America SEC-2415UL Manuel d'utilisation
Page 11
![background image](/manuals/415611/11/background.png)
10 | SAMLEX AMERICA INC.
SAMLEX AMERICA INC. | 11
seCtIOn 5 |
Installation & Charger Operation
plug to mate with the 230 VAC out-
let. cAUtion: the new plug should
have 3 poles i.e. line (l) , neutral(n)
and earth ground. color code for the
power cord conductors is:
- line (l) - Black
- neutral (n) - white
- earth ground - green
Preparing the charger For
operation: Selecting the type
of Battery And charging Stages
The Float Voltage and Boost Voltage (Also
called Absorption or Overcharge Voltage)
of different types of Lead Acid Batteries
are different. Also, when a charger is used
to charge a battery and simultaneously
supply a load , the Boost Stage is required
to be disabled to prevent overcharging of
the battery. A DIP Switch is provided on
top of the output terminals for selecting
the battery type and for disabling the
Boost Stage when charging loaded batter-
ies. The following selections can be made
with the help of the DIP Switch.
cAUtion! Do not change the DiP Switch
setting when the charger is operating. Al-
ways change the DiP Switch setting when
the charger is off, i.e. after disconnecting
the charger from the Ac input power.
note: the voltages are for a temperature
of 80°F.
cAUtion! Please ensure that the position
no. 4 of the DiP switch (S1-on & S2-on) is
neVeR selected.
DIP SWITCH SETTINGS: SEC-1215UL/SEC-1230UL
S1
S2
float
boost
battery
Type
Charging
Stages
off *
ON *
13.5 V *
14.4 V *
flooded /
AGM *
3 Stages
(Stages 1, 2, 3)
ON *
off
13.5 V
14.0 V
Gel Cell
3 Stages
(Stages 1, 2, 3)
off
off
13.5 V
Disabled
Battery with
Load
2 Stages
(Stages 1, 3)
ON
ON
caution! Do not use this setting
* factory pre-set in this position
DIP SWITCH SETTINGS - SEC-2415UL
S1
S2
float
boost
Battery Type
Charging
Stages
off *
ON *
27 V *
28.8 V *
flooded /
AGM *
3 Stages
(Stages 1, 2, 3)
ON
off
27 V
28.0 V
Gel Cell
3 Stages
(Stages 1, 2, 3)
off
off
27 V
Disabled
Battery with
load
2 Stages
(Stages 1, 3)
ON
ON
caution! Do not use this setting