DISPLAY

ground fault / leakage. It compares the current sent to the load side and returned

back from the load side. If the returned current is less by more than 5 to 7 mA

(this loss of returned current will be due to ground fault / leakage on the load

side), the switch trips and disconnects the AC load from the AC source. When the

GfCI has tripped due to ground fault / leakage, it can be reset by pressing the

reset button.

for the reset button to operate and reset the GfCI, AC power is required to be

present on the Line Side (input side) of the GfCI. If AC power is not available on

the Line Side (input side) of the GfCI, the GfCI will not reset.

When the GfCI trips due to leakage on the Load Side, the following symptoms

will be seen:

On the GFCI

• The Green LeD light on the GfCI will be switched off

On the Inverter

• Green LeD on the front panel of the inverter will continue to remain

lighted

• Internally, the inverter will still be working normally and the rated AC

output voltage will be available on the internal Line Side of the GfCI,

but not on the external Load Side of the fGCI due to trippped relay in

the GfCI.

On the LCD Display

• Power bar graph is switched off
• backlight is dimmed
• only the DC input voltage is displayed

When the output side of the GfCI outlet of the inverter trips due to ground

fault / leakage on the load side, the inverter will still be operating normally and

AC power will still be available on the Line Side (input side) of the GfCI (but not

on the output side of the GfCI). Thus, “OUTPUT FAULT” message will NOT be

displayed when the GFCI has tripped due to ground fault / leakage on the Load

Side. Use the “reset” button on the GfCI to reset the mechanical switch to the

on position after removing the cause of the ground fault.