Setup and Commissioning
Settings can be performed before
fitting the sensor unit. If you wish
to change the settings again
after fitting the sensor unit, the
catch must first be released with
a flat-bladed screwdriver and the
sensor unit must be removed (see
illustration below).
When this is done, the light
fixture automatically switches to
continuous operation. On fitting
the sensor unit, an approximately
45 second measuring phase is
initiated. The red LED flashes
during this period.
10
Setup and Commissioning
Light level
The light level feature allows
lighting to remain OFF
during daylight, regardless of
occupancy. Daytime operation
is at 200 footcandles (factory
setting). Nighttime operation is
at .2 footcandles. Factory setting
is 200 fc.
The adjusting screw must be
set to daytime operation (200
fc) when adjusting the detection
zone and performing the function
test in daylight.
.2 – 200 fc
approx. 5 sec. – 20 min.
Time delay
Time delay is the period of time
lights remain on after the last
detection. Adjustment ranges
from 5 seconds to 20 minutes.
Factory setting is 5 seconds.
The shortest time delay setting is
recommended when adjusting the
detection zone and performing the
function test.
.2 – 200 fc
approx. 5 sec. – 20 min.
11
approx. 5 sec. – 20 min.