Wiring, Wiring operation – STEINEL IS D360-24 Manuel d'utilisation
Page 5

www.steinel.net
(800) 852-4343
www.steinel.net
(800) 852-4343
Wiring
When installing, make sure power
has been switched off at the
breaker and check that the circuit
is dead with a voltage tester.
18 AWG 3 conductor wire is
recommended for connection to a
Steinel power pack.
Red - (+24 VDC)
Black - (-24 VDC)
Blue - (Control)
8
Wiring with TR 150 Power Pack to a
building management system
Wiring
Operation
The IS D360-24 works with
STEINEL power packs to control
lighting based on occupancy and
daylight.
Manual operation
• A line voltage or low voltage
switch may be used for manual
off control when the power
pack is in automatic on mode
• For manual on only operation,
a low voltage momentary
switch is required along with
a STEINEL power pack set in
manual on mode
Light level function
The sensors incorporate a built-in
light level sensor which keeps
lighting off during daylight hours,
regardless of occupancy.
9
Wiring with TR 100
Power Pack
BLUE (CONTROL)
BLACK (-24VDC)
RED (+24VDC)
GRAY (MOMENTARY SWITCH)
YELLOW/RED (NORMALLY OPEN)
YELLOW (RELAY COMMON)
YELLOW/BLACK (NORMALLY CLOSED)
ORANGE (OVERRIDE ON)
BROWN (OVERRIDE OFF)
Normally open momentary contact switch
Maintained contact switch
WHITE (NEUTRAL)
BLACK (HOT)
RED (RELA
Y)
RED (RELA
Y)
BLUE (CONTROL)
BLACK (-24VDC)
RED (+24VDC)
Model#
TR150
Power Pack
LINE VOLTAGE
SWITCH
24VDC
Sensor
Isolated Relay
NORMALLY OPEN
RELAY COMMON
NORMALLY CLOSED
Building Management
System
LOAD
NEUTRAL
HOT
Symbol List
WHITE (NEUTRAL)
BLACK (HOT)
RED (RELA
Y)
RED (RELA
Y)
LOAD
NEUTRAL
HOT
Model#
TR100
Power Pack
24VDC
Sensor
LINE VOLTAGE
SWITCH
BLUE (CONTROL)
BLACK (-24VDC)
RED (+24VDC)
BLUE (CONTROL)
BLACK (-24VDC)
RED (+24VDC)
GRAY (MOMENTARY SWITCH)
Momentary switch