Wiring, Wiring operation – STEINEL IS D360-24 Manuel d'utilisation

Page 5

Advertising
background image

www.steinel.net

(800) 852-4343

www.steinel.net

(800) 852-4343

Wiring

When installing, make sure power
has been switched off at the
breaker and check that the circuit
is dead with a voltage tester.
18 AWG 3 conductor wire is
recommended for connection to a
Steinel power pack.

Red - (+24 VDC)
Black - (-24 VDC)
Blue - (Control)

8

Wiring with TR 150 Power Pack to a
building management system

Wiring

Operation

The IS D360-24 works with
STEINEL power packs to control
lighting based on occupancy and
daylight.

Manual operation

• A line voltage or low voltage

switch may be used for manual
off control when the power
pack is in automatic on mode

• For manual on only operation,

a low voltage momentary
switch is required along with
a STEINEL power pack set in
manual on mode

Light level function
The sensors incorporate a built-in
light level sensor which keeps
lighting off during daylight hours,
regardless of occupancy.

9

Wiring with TR 100
Power Pack

BLUE (CONTROL)
BLACK (-24VDC)
RED (+24VDC)
GRAY (MOMENTARY SWITCH)
YELLOW/RED (NORMALLY OPEN)
YELLOW (RELAY COMMON)
YELLOW/BLACK (NORMALLY CLOSED)
ORANGE (OVERRIDE ON)
BROWN (OVERRIDE OFF)

Normally open momentary contact switch

Maintained contact switch

WHITE (NEUTRAL)

BLACK (HOT)

RED (RELA

Y)

RED (RELA

Y)

BLUE (CONTROL)

BLACK (-24VDC)

RED (+24VDC)

Model#
TR150
Power Pack

LINE VOLTAGE

SWITCH

24VDC
Sensor

Isolated Relay

NORMALLY OPEN
RELAY COMMON
NORMALLY CLOSED

Building Management

System

LOAD

NEUTRAL

HOT

Symbol List

WHITE (NEUTRAL)

BLACK (HOT)

RED (RELA

Y)

RED (RELA

Y)

LOAD

NEUTRAL

HOT

Model#
TR100
Power Pack

24VDC
Sensor

LINE VOLTAGE

SWITCH

BLUE (CONTROL)

BLACK (-24VDC)

RED (+24VDC)

BLUE (CONTROL)
BLACK (-24VDC)
RED (+24VDC)
GRAY (MOMENTARY SWITCH)

Momentary switch

Advertising