SLC 500 BASIC and BASIC-T Modules 25
Publication 1746-IN009B-EN-P - August 2005
Operating Voltage and Current Requirement
Component
Operating Voltage
Current Requirement
Hand-Held Terminal
24V dc
0.105 A
Data Table Access Module
24V dc
0.104 A
Interface Converter
24V dc
0.060 A
IMPORTANT
The module receives its power from the SLC backplane. The
power consumption of the module must be taken into
consideration when planning your SLC 500 system. Refer to the
documentation supplied with your SLC 500 fixed or modular
controller for additional information on power supplies and
current requirements.
Communication
Maximum Distance Allowed in Meters (Feet)
Rate (bps)
RS-232
RS-423
RS-422
RS-485
300
15 (50)
1230 (4000)
1230 (4000)
1230 (4000)
600
15 (50)
920 (3000)
1230 (4000)
1230 (4000)
1200
15 (50)
770 (2500)
1230 (4000)
1230 (4000)
4800
15 (50)
245 (800)
1230 (4000)
1230 (4000)
9600
15 (50)
120 (400)
1230 (4000)
1230 (4000)
19200
15 (50)
60 (200)
1230 (4000)
1230 (4000)
IMPORTANT
Use the RS-423 jumper settings when communicating in RS-232
mode.