Rockwell Automation 1746-RT34 SLC 500 Thermocouple/mV Input Module Terminal Block Installation Instructions Manuel d'utilisation
Installation instructions

Publication 1746-IN018B-EN-P
Installation Instructions
SLC 500™ Thermocouple/mV Input
Module Terminal Block
(Catalog Number 1746-RT34)
To remove the terminal block:
1.
1.
1.
1. Loosen the two terminal block release screws. To avoid cracking the terminal
block, alternate between screws as you remove them.
2.
2.
2.
2. Using a 2.5 mm (0.1 in.) slot-head screwdriver or needle-nose pliers, carefully pry
the terminal block loose. When removing or installing the terminal block be
careful not to damage the CJC sensors.
!
ATTENTION
Possible Equipment Operation:
Before wiring your module, always disconnect power from the
SLC 500 system and from any other source to the module.
Failure to observe this precaution can cause unintended
equipment operation and damage.
Terminal Block
Release Screws
CJC Sensors
CJC Sensors
Terminal Block
Release Screws
Recommended Torque:
wiring screws: 0.25 Nm (2.2 in-lb)
release screws: 0.25 Nm (2.2 in-lb)