Warning – Napoleon Fireplaces STARfire 52 - HDX52 Manuel d'utilisation
Page 27

27
W415-1276 / A / 05.09.14
EN
IMPORTANT: The HDX52 requires a minimum inside enclosure height of 88" (2235mm), measured from the
bottom of the appliance. For temperature requirements, this area must be left unobstructed. It is recommended
that the enclosure be ventilated at the top and bottom to circulate the air.
88"
2235mm *
MINIMUM
ENCLOSURE
HEIGHT
41 7/8"
1064mm
MINIMUM
71 1/2"
1816mm
MINIMUM
PLUS RISE *
2" 51mm
5" 127mm
11 1/2"
292mm
MINIMUM **
MINIMUM
6"
152mm
COMBUSTIBLE
MATERIAL
TOP OF ENCLOSURE
BRICK
STEEL STUD
FRAMING
TOP OF
FIREPLACE
OPENING
0” (0mm) IF NON-
COMBUSTIBLE FINISHING
IS USED SUCH AS BRICK
AND STONE
NON-COMBUSTIBLE
MATERIAL
NOTE: JOINT COMPOUNDS AND TAPES
THAT ARE RESILIENT TO HEAT AND
CRACKING SHOULD BE USED WHEN
TAPING AND MUDDING SEAMS.
SAFETY SCREEN
** Within the appliance enclosure a 11 1/2" (292mm) clearance between the top of the vent pipe and combustible material
is required. All other clearance, including where the vent exits the enclosure are subject to 2" (51mm) to the sides and
bottom and 5" (127mm) to the top for horizontal and 1" (25mm) for vertical.
!
WARNING
RISK OF FIRE!
THE FRONT OF THE APPLIANCE MUST BE FINISHED WITH ANY NON-COMBUSTIBLE MATERIALS
SUCH AS BRICK, MARBLE, GRANITE, ETC., PROVIDED THAT THESE MATERIALS DO NOT COVER
THE APPLIANCE OPENING.
THE STEEL STUD FRAMING KITS WITH CEMENT BOARD PROVIDED MUST BE INSTALLED.
5.2 MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES