Light level teach mode - RHB 300, RHB 200
The light level teach mode reads the ambient
light level in the space and selects this amount
for the light level setting.

• Turn the light level setting to
• After 10 seconds, the value of the ambient

brightness is saved.

• This value is also available after a power

failure if the potentiometer is set to teach
mode at power up.

Time delay RHB 300, RHB 200
Time delay is the period of time lights remain
on after the last detection. Adjustment ranges
from 35 seconds to 30 minutes. Factory
setting is 15 minutes.

After setup and commissioning tests are
complete, adjust the time delay and light level
settings to fi t the application needs.

Time

ON

1 2 3

4

Time Delay DIP Switch

1

ON

ON

OFF

ON

ON

OFF

OFF

OFF

N/A

2

ON

OFF

ON

OFF

ON

ON

OFF

OFF

N/A

3

ON

OFF

ON

ON

OFF

OFF

ON

OFF

N/A

4

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

ON

Time

35 sec

1 min

5 min

10 min

15 min

20 min

25 min

30 min

override

Light level: .2 (night) to 200 (day) footcandles

Low

High

Setup & Commissioning

Setup & Commissioning

RHB 300 Coverage
The RHB 300 contains three pyroelectric
sensors to detect occupancy. At an
installation height of 8 to 45 feet, maximum
reach is 22 feet radial and 60 feet tangential.
If needed, the detection zone can be
adjusted (see below).
Coverage may vary depending on mounting
height and environmental conditions.

RHB 200 Coverage
The RHB 200 contains two pyroelectric
sensors to detect occupancy and has an
aisle way coverage of up to 100 feet when
mounted at 40 ft. If needed, the detection
zone can be adjusted with a lens cover (see
below).
In addition, the view of the RHB 200 can
be rotated 90 degrees. To do this, remove
the sensor housing from the back box
by pressing the tabs on either side of the
sensor.
Coverage may vary depending on mounting
height and environmental conditions.

10
20
30
40

40 ft

50

50

40

40

35 ft

22 ft 22 ft

35 ft

10
20
30
40

radial

tangential

40 ft

13 ft

50 ft

53 ft 53 ft

50 ft

www.steinel.net (800) 852-4343

www.steinel.net (800) 852-4343

10

11

Groups - RHB 300, RHB 200, RM 50
The 5 position DIP switch on all STEINEL
wireless devices can be used for setting
32 different addresses or groups.
All devices in a group must have the same DIP
switch setting. The ON switching commands
only applies within a group.
Use the “Wireless Zone Worksheet” on page
13 to document your lighting control groups.

Test mode - RHB 300, RHB 200

• Ensure that the sensor is in test mode.

- set time delay to minimum setting of

35 seconds

- set light level to maximum (“day” setting,

light level function overridden - factory
setting)

• Turn power ON at the circuit breaker (lights

will turn ON). After a warm up period of up
to one minute, lights will turn OFF if the
sensor does not detect motion.

• Walk in view of sensor, lights should turn

ON. Be still for 35 seconds and lights
should turn OFF.

Light level - RHB 300, RHB 200
The light level feature allows lighting to remain
OFF during daylight, regardless of occupancy.
Daytime operation is at 200 footcandles
(factory setting). Nighttime operation is at
.2 footcandles.