CAMPO EQUIPMENT BLAZE 600 D Manuel d'utilisation
Page 10

CAMPO EQUIPMENT CO. LTD. (ECOBLAZE)
6 Carson Court, Brampton, ON, CANADA, L6T 4P8
Tel: (905) 793-2525 | Fax: (905) 793-8768 | www.campoequipment.com
SIDES
6 inches
BURNER END
2 feet
DISCHARGE END
10 feet
VENT CONNECTOR
18 inches
COMBUSTIBLE FLOOR
6 feet
FLUE PIPE CONNECTIONS
VENT TO OUTDOORS
FOR INSTALLATION ON NON-COMBUSTIBLE FLOORS ONLY
When the heater is connected to a flue pipe the flue pipe shall terminate in a vertical section at
least two feet long. Horizontal runs should have rise ratio of 1 in 10 away from the heater. Where
down drafts are liable to occur a vent cap should be used. All venting should correspond with the
CSA B139 standard or local codes.
CAUTION: HEATER FLUE TEMPERATURES CAN REACH 900F TO 1000F THEREFORE IT IS A
RANGE THAT IS BOTH HAZARDOUS TO HUMANS AND HIGHER THAN THE AUTO-IGNITION
TEMPERATURES OF MANY MATERIALS. THEREFORE EXERCISE CAUTION IN HEATER
PLACEMENT AND THE USE OF AN INSULATED GUARD AND STACK IS HIGHLY
RECOMMENDED
.
Horizontal venting runs shall always terminate with a minimum 24” vertical.
NOTE: FOR OPTIMAL COMBUSTION PERFORMANCE A 30” C-VENT FLUE EXTENSION WITH
RAIN CAP IS RECOMMENDED AT ALL TIMES.