Report unit number, Assign unit number, Set number of floats – VEGA VEGABAR 87 Modbus and Levelmaster protocol - Operating Instructions Manuel d'utilisation
Page 71: Set baud rate

71
10 Annexe
VEGABAR 87 • Protocole Modbus et Levelmaster
46297-FR-131120
Report Unit Number
Request:
Paramètres
Length
Code/Data
Report Unit Number
5 characters ASCII
U**N?
Response:
Paramètres
Length
Code/Data
Report Level (and Temperature)
6 characters ASCII
UuuNnn
Assign Unit Number
Request:
Paramètres
Length
Code/Data
Assign Unit Number
6 characters ASCII
UuuNnn
Response:
Paramètres
Length
Code/Data
Assign Unit Number
6 characters ASCII
UuuNOK
uu = new Address
Set number of Floats
Request:
Paramètres
Length
Code/Data
Set number of Floats
5 characters ASCII
UuuFn
Response:
Paramètres
Length
Code/Data
Set number of Floats
6 characters ASCII
UuuFOK
Si le nombre est remis à 0, le niveau n'est pas signalé.
Set Baud Rate
Request:
Paramètres
Length
Code/Data
Set Baud Rate
8 (12) characters ASCII
UuuBbbbb[b][pds]
Bbbbb[b] = 1200, 9600 (default)
pds = parity, data length, stop bit
(optional)
parity: none = 81, even = 71 (de-
fault), odd = 71