Table 5 connection type / wire size range, 7deohýè, 7deohýç – Liebert Series 300 Manuel d'utilisation
Page 25: Э7deoh è, Ý7deoh ç, Ý7deoh èý, 7deoh ç

Installation 17
Table 5
Connection Type / Wire Size Range
Connection Type
UPS Module
Rating
kVA
AC Input
Battery
Bypass Input
& AC Output
Neutral
Ground
10 - 30
Compression
lug
#14 to #1/0
Compression
lug
#14 to #1/0
Compression
lug
#14 to #1/0
Compression
lug
#14 to #1/0
Ground studs
3/8" - 16 x 1.00"
Lug required
40 - 50
Compression
lug
#6 to 250 kcmil
Compression
lug
#6 to 250 kcmil
Compression
lug
#6 to 250 kcmil
Natural studs
3/8" - 16 x 1.00"
Lug required
Ground studs
3/8" - 16 x 1.00"
Lug required
65 - 125
Bus bars (2” x 3-1/4”) with connecting hardware (3/8”) are provided for all power wiring
terminations. A field-supplied lug is required.
Use factory supplied connections for terminations where they are provided. Refer to Figure 16 for field-
supplied wiring termination details. Use commercially available UL listed solderless lugs for the wire size
required for your application. Connect wire to the lug using tool and procedure specified by the lug
manufacturer.
Table 6
Torque Specifications (Unless Otherwise Labeled)
Nut and Bolt Combinations
Bolt Shaft Size
Grade 2
Standard
Electrical Connections
with Belleville Washers
Lb-in
N-m
Lb-in
N-m
1/4
53
6.0
46
5.2
5/16
107
12.1
60
6.8
3/8
192
21.7
95
10.7
1/2
428
48.4
256
28.9
Terminal Block Compression Lugs
UPS Module
Rating
kVA
Wiring
Wire Size or
Range
Lb-in
N-m
10 - 125
Control
#22 - #14
3.5 to 5.3
0.4 to 0.6
10 - 30
Power
#6 - #1/0
50
5.6
40 - 50
Power
#6
250
28.2
250 kcmil
275
31.1