Basler Electric BE1-11 Modbus Protocol Manuel d'utilisation
Page 122

116
9424200774 Rev B
Tableau de registre
BE1-11
Nom
Description
Group
e
Registr
e
Type
Octet
s
Autoris
é en
écriture
Unité
Plage
Style
51-7
Constante TD
SG0
22194
4870*
Float
4
L É
s/o
0 - 9,9
FGIT
51-7
Constante A
SG0
22196
4872*
Float
4
L É
s/o
0 - 600
FGIT
51-7
Constante B
SG0
22198
4874*
Float
4
L É
s/o
0 - 25
FGIT
51-7
Constante C
SG0
22200
4876*
Float
4
L É
s/o
0 - 1
FGIT
51-7
Constante N
SG0
22202
4878*
Float
4
L É
s/o
0,5 - 2,5
FGIT
51-7
Constante R
SG0
22204
4880*
Float
4
L É
s/o
0 - 30
FGIT
51-7
Consigne de
retenue de
tension
SG0
22206
4882*
Float
4
L É
Volt
30 - 250
FGIT
51-7
Mode de retenue
de tension
SG0
22208
4884*
Uint32
4
L É
s/o
Désactivé=0
Contrôlée=1
Retenue=2
FGIT
51-7
Mode
SG1
22210
4886*
Uint32
4
L É
s/o
Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9
FGIT
51-7
Source
SG1
22212
Uint32
4
L É
s/o
TC1=0
TC2=1
FGIT
51-7
Enclenchement
SG1
22214
4888*
Float
4
L É
Ampère
0,5 - 16
FGIT
51-7
Indice de courbe
SG1
22216
4890*
Uint32
4
L É
s/o
S1=0, S2=1, L1=2, L2=3,
D=4, M=5, I1=6, I2=7,
V1=8, V2=9, E1=10,
E2=11, A=12, B=13, C=14,
G=15, F=16, 46=17, P=18,
T1=19, T2=20, T3=21,
T4=22, A1=23, B1=24,
C1=25, D1=26, E3=27,
F1=28
FGIT
51-7
Sens
SG1
22218
4892*
Uint32
4
L É
s/o
Sens entrant=0
Sens sortant=1
Non directionnel=2
FGIT
51-7
Utilisation de la
réinitialisation
instantanée
SG1
22220
4894*
Uint32
4
L É
s/o
Intégrée=0
Instantanée=1
FGIT
51-7
Constante TD
SG1
22222
4896*
Float
4
L É
s/o
0 - 9,9
FGIT
51-7
Constante A
SG1
22224
4898*
Float
4
L É
s/o
0 - 600
FGIT
51-7
Constante B
SG1
22226
4900*
Float
4
L É
s/o
0 - 25
FGIT
51-7
Constante C
SG1
22228
4902*
Float
4
L É
s/o
0 - 1
FGIT
51-7
Constante N
SG1
22230
4904*
Float
4
L É
s/o
0,5 - 2,5
FGIT
51-7
Constante R
SG1
22232
4906*
Float
4
L É
s/o
0 - 30
FGIT
51-7
Consigne de
retenue de
tension
SG1
22234
4908*
Float
4
L É
Volt
30 - 250
FGIT
51-7
Mode de retenue
de tension
SG1
22236
4910*
Uint32
4
L É
s/o
Désactivé=0
Contrôlée=1
Retenue=2
FGIT
51-7
Mode
SG2
22238
4912*
Uint32
4
L É
s/o
Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9
FGIT
51-7
Source
SG2
22240
Uint32
4
L É
s/o
TC1=0
TC2=1
FGIT
51-7
Enclenchement
SG2
22242
4914*
Float
4
L É
Ampère
0,5 - 16
FGIT