Basler Electric BE1-11 Modbus Protocol Manuel d'utilisation
Page 109

9424200774 Rev B
103
BE1-11
Tableau de registre
Nom
Description
Group
e
Registr
e
Type
Octet
s
Autoris
é en
écriture
Unité
Plage
Style
51-1
Mode de retenue
de tension
SG2
21592
4312*
Uint32
4
L É
s/o
Désactivé=0
Contrôlée=1
Retenue=2
FGIM
T
51-1
Mode
SG3
21594
4314*
Uint32
4
L É
s/o
Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9
FGIM
T
51-1
Source
SG3
21596
Uint32
4
L É
s/o
TC1=0
TC2=1
FGIM
T
51-1
Enclenchement
SG3
21598
4316*
Float
4
L É
Ampère
0,5 - 16
FGIM
T
51-1
Indice de courbe
SG3
21600
4318*
Uint32
4
L É
s/o
S1=0, S2=1, L1=2, L2=3,
D=4, M=5, I1=6, I2=7,
V1=8, V2=9, E1=10,
E2=11, A=12, B=13, C=14,
G=15, F=16, 46=17, P=18,
T1=19, T2=20, T3=21,
T4=22, A1=23, B1=24,
C1=25, D1=26, E3=27,
F1=28
FGIM
T
51-1
Sens
SG3
21602
4320*
Uint32
4
L É
s/o
Sens entrant=0
Sens sortant=1
Non directionnel=2
FGIT
51-1
Utilisation de la
réinitialisation
instantanée
SG3
21604
4322*
Uint32
4
L É
s/o
Intégrée=0
Instantanée=1
FGIM
T
51-1
Constante TD
SG3
21606
4324*
Float
4
L É
s/o
0 - 9,9
FGIM
T
51-1
Constante A
SG3
21608
4326*
Float
4
L É
s/o
0 - 600
FGIM
T
51-1
Constante B
SG3
21610
4328*
Float
4
L É
s/o
0 - 25
FGIM
T
51-1
Constante C
SG3
21612
4330*
Float
4
L É
s/o
0 - 1
FGIM
T
51-1
Constante N
SG3
21614
4332*
Float
4
L É
s/o
0,5 - 2,5
FGIM
T
51-1
Constante R
SG3
21616
4334*
Float
4
L É
s/o
0 - 30
FGIM
T
51-1
Consigne de
retenue de
tension
SG3
21618
4336*
Float
4
L É
Volt
30 - 250
FGIM
T
51-1
Mode de retenue
de tension
SG3
21620
4338*
Uint32
4
L É
s/o
Désactivé=0
Contrôlée=1
Retenue=2
FGIM
T
51-2
Mode
SG0
21622
4340*
Uint32
4
L É
s/o
Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9
FGIM
T
51-2
Source
SG0
21624
Uint32
4
L É
s/o
TC1=0 TC2=1
FGIM
T
51-2
Enclenchement
SG0
21626
4342*
Float
4
L É
Ampère
0,5 - 16
FGIM
T
51-2
Indice de courbe
SG0
21628
4344*
Uint32
4
L É
s/o
S1=0, S2=1, L1=2, L2=3,
D=4, M=5, I1=6, I2=7,
V1=8, V2=9, E1=10,
E2=11, A=12, B=13, C=14,
G=15, F=16, 46=17, P=18,
T1=19, T2=20, T3=21,
T4=22, A1=23, B1=24,
C1=25, D1=26, E3=27,
F1=28
FGIM
T
51-2
Sens
SG0
21630
4346*
Uint32
4
L É
s/o
Sens entrant=0
Sens sortant=1
Non directionnel=2
FGIT
51-2
Utilisation de la
réinitialisation
instantanée
SG0
21632
4348*
Uint32
4
L É
s/o
Intégrée=0
Instantanée=1
FGIM
T