Celduc Temperature controller ECOM Manuel d'utilisation
Page 59

60
ECOM0010 - User manual
10
PQLW
Minimum Integral Time
Selects the min. integral time value selectable by the
automatic tuning
Word modbus 2010
0..9999 tenths of seconds. > Default: 100
E.g.: 100 = 10.0 seconds
11
SE
Proportional Band
Process inertia in units (Ex: if temperature in °C)
Word modbus 2011
LabSoftView:
Default: 0
E.g. : 10 = 10
Modbus:
UFOUIT
E.g. : 10 = 1.0
0 = ON/OFF if also
WL
is equal to 0.
12
WL
Integral Time
Process inertia in seconds
Word modbus 2012 - 0 = Integral action deactivated
LabSoftView:
0..999.9 seconds >
Default: 0
E.g. : 40 = 40 seconds
Modbus:
0..9999 tenths of seconds
E.g. : 400 = 40.0 seconds
0 = Integral action disabled.
13
WG
Derivative Time
Normally ¼ of integral time.
Word modbus 2013 - 0 = Action dérivée désactivée.
LabSoftView:
0..999.9 seconds > Default:
0
E.g. : 10 = 10 seconds
Modbus:
0..9999 tenths of seconds
E.g. : 100 = 10.0 seconds
0 = Derivative action disabled.