ECOM0010 - User manual
Modbus
address
Description
Read
Write
Reset
value
1007
Led status (0=off, 1=on)
Bit0 = Red led
Bit1 = Yellow led
Bit2 = Green led
RO
0
1008
Alarm status (0=absent, 1=present)
Bit0 = Alarm 1
RO
0
1009
Error flags
Bit0 = Cold junction error
Bit1 = Process error (sensor)
Bit2 = Error in eeprom writing
Bit3 = Error in eeprom reading
Bit4 = Error missing calibration
Bit5 = Generic error
Bit6 = Hardware error
Bit7 = Error H.B.A.* (SSR in short circuit)
Bit8 = Error H.B.A.* (SSR/open charge)
Bit9 = Error H.B.A.* (partial break of the
charge)
RO
0
1010
Cold junction temperature (degree with
tenth)
RO
?
1011
Hot output percentage (0-10000)
R/W
0
1012
Cold output percentage (0-10000)
RO
0
1013
Current transformer value (ampere with
tenth)
RO
?
1014
Current transformer ON (ampere with
tenth)
RO
?
1015
Current transformer OFF (ampere with
tenth)
RO
?
1016
Push button status
RO
0
1017
Dip value
RO
0
2001
Parameter 1
R/W EEPROM