Gas Connection

PRESSURE REGULATION AND TESTING
Each oven has been adjusted at the factory to op-

erate with the type of gas specified on the rating

plate attached to the left side of the control panel.
Each oven is supplied with a regulator to maintain

the proper gas pressure.

The regulator is essen-

tial to the proper operation of the oven and

should not be removed. It is preset to provide the

oven with 3.5” W.C. (0.87 kPa) while the flame is

on. The regulator is located on top of the gas valve,

between the manual shutoff and solenoid valves.
DO NOT INSTALL AN ADDITIONAL REGULATOR

WHERE THE OVEN CONNECTS TO THE GAS

SUPPLY UNLESS THE SUPPLY EXCEEDS THE

MAXIMUM.
NOTE: The maximum gas supply pressure to the

oven is 10.5” W.C. (2.61 kPa). The mini-

mum gas supply pressure to the oven is

4.5” W.C. (1.1 kPa).

Installation must conform with local codes, or in

the absence of local codes, with the

National Fuel

Gas Code, NFPA54/ANSI Z223.1---Latest Edition,

the Natural Gas Installation Code CAN/CGA-

B149.1 or the Propane Installation Code, CAN/

CGA-B149.2 as applicable.
The oven and its individual shutoff valve must be

disconnected from the gas supply piping system

during any pressure testing of that system at test

pressures in excess of 1/2 psig (3.45kPa).
The oven must be isolated from the gas supply

piping system by closing its individual manual

shutoff valve during any pressure testing of the

gas piping system at test pressures equal or less

than 1/2 psig (3.45kPa).

Gas Connection 2” (51 mm)

Gas Connection 2” (51 mm)

Figure 11