Warning – Napoleon Fireplaces IR3-1 Manuel d'utilisation
Page 11

W415-1198 / 05.24.13
11
EN
Combustible mantel clearance can vary
according to the mantel depth. Use the
graph to help evaluate the clearance
needed. These same requirements
apply to any combustibles protruding
on either side of the appliance.
H
D
F
G
MANTEL DEPTH
0” (mm)
+
(
,
*
+
7
0
$
1
7
(
/
E
C
B
A
!
WARNING
RISK OF FIRE, MAINTAIN ALL SPECIFIED AIR SPACE CLEARANCES TO COMBUSTIBLES. FAILURE
TO COMPLY WITH THESE INSTRUCTIONS MAY CAUSE A FIRE OR CAUSE THE APPLIANCE TO
OVERHEAT. ENSURE ALL CLEARANCES (I.E. BACK, SIDE, TOP, VENT, MANTEL, FRONT, ETC.) ARE
CLEARLY MAINTAINED.
WHEN USING PAINT OR LACQUER TO FINISH THE MANTEL, THE PAINT OR LACQUER MUST BE
HEAT RESISTANT TO PREVENT DISCOLOURATION.
73.1
4.1 MINIMUM MANTEL CLEARANCES
D
A
B
C
E
F
H
G
20
1
/
2
”
(520.7mm)
4.2 DOOR REMOVAL AND INSTALLATION
!
WARNING
GLASS MAY BE HOT, DO NOT TOUCH GLASS UNTIL COOLED.
THE DOOR LATCHES ARE PART OF A SAFETY SYSTEM AND MUST BE PROPERLY ENGAGED. DO
NOT OPERATE THE APPLIANCE WITH LATCHES DISENGAGED.
FACING AND/OR FINISHING MATERIALS MUST NOT INTERFERE WITH AIR FLOW THROUGH AIR
OPENINGS, LOUVRES OPENINGS, OPERATION OF LOUVRES OR DOORS OR ACCESS FOR
SERVICE. OBSERVE ALL CLEARANCES WHEN APPLYING COMBUSTIBLE MATERIALS.
BEFORE DOOR IS REMOVED TURN THE APPLIANCE OFF AND WAIT UNTIL APPLIANCE IS COOL TO
THE TOUCH. DOORS ARE HEAVY AND FRAGILE SO HANDLE WITH CARE.
75.1
DOOR LATCH
The optional front must be removed to allow the door to be opened or closed. Release the top left and right
door latches, located at the top of the door. Tilt forward and lift from slots.
MANTEL DIMENSIONS
Ref
Height
Ref
Depth
A
17" (431.8mm)
E
6" (152.4mm)
B
16" (406.4mm)
F
5" (127mm)
C
15" (381mm)
G
4" (101.6mm)
D
14” (355.6mm)
H
3" (76.2mm)