Warning – Napoleon Fireplaces Vector 62 - LHD62 Manuel d'utilisation
Page 28

W415-1068 / B / 01.02.14
28
EN
* Within the appliance enclosure a minimum 7” (178mm) clearance between the top of the vent pipe and
combustible materials is required. All other clearances within the enclosure, including where the vent pipe exits
the enclosure are subject to 2” (51mm) to the sides and bottom and 3” (76mm) to the top for horizontal and 1”
(25mm) for vertical.
** See venting section.
IMPORTANT:
The LHD62 requires a minimum inside enclosure height of 96” (2.4m), measured from the
bottom of the appliance. For temperature requirements, this area must be left unobstructed. It is recommended
that the enclosure be ventilated at the top and bottom to circulate the hot air.
Before fi nishing in the appliance test the operation using the remote control, cycling it through all of its different
modes, see “OPERATION” section. Check pressure readings, see “PILOT BURNER ADJUSTMENT” section.
Once fi nished in, access to the control components can only be done through the inside of the appliance.
5.1 MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES
!
WARNING
THE FRONT OF THE APPLIANCE MUST BE FINISHED WITH ANY NON-COMBUSTIBLE MATERIALS
SUCH AS BRICK, MARBLE, GRANITE, ETC., AS LONG AS THESE MATERIALS NEVER OVERHANG
INTO THE APPLIANCE OPENING.
96”
(2438mm)
MINIMUM
ENCLOSURE
HEIGHT
TOP OF
ENCLOSURE
TOP OF
APPLIANCE
OPENING
7” (178mm)
MINIMUM
NOTE: JOINT COMPOUNDS AND TAPES
THAT ARE RESILIENT TO HEAT AND
CRACKING SHOULD BE USED WHEN
TAPING AND MUDDING SEAMS.
STEEL
STUD
FRAME
28”
(711mm)
MINIMUM
68”
(1727mm)
MINIMUM
COMBUSTIBLE
NON-COMBUSTIBLE
COMBUSTIBLE
9”
(228mm)
TO SIDEWALL
DRYWALL