*HORIZONTAL VENT SECTIONS:
A minimum clearance of 3” (76mm) to the top and 2” (51mm) to the
sides and bottom of the vent pipe on all horizontal runs to combustibles is required. Horizontal vent sections
within enclosures require a minimum clearance of 7” (178mm) at the top of the vent pipe, see “MINIMUM
CLEARANCE TO COMBUSTIBLE ENCLOSURES” section. Use fi restop assembly W010-2883 (supplied).
*VERTICAL VENT SECTIONS:
A minimum of 1” (25mm) all around the vent pipe on all vertical runs
to combustibles is required except for clearances in appliance enclosures. Vertical vent sections within
enclosures require a minimum clearance of 2” (51mm) around the vent pipe. Use fi restop spacer W500-0681
(not supplied).