Warning – Napoleon Fireplaces Vittoria - GD19 Manuel d'utilisation
Page 36

36
W415-1004 / B / 08.10.12
Mantel clearance can vary according to the mantel depth. Use the graph to help evaluate the clearance
needed.
Combustible materials must be installed fl ush with the front of the appliance but must not cover any of the
black face-area of the appliance. Non-combustible material (brick, stone or ceramic tile) may protrude past the
face of the appliance.
MANTEL DEPTH
M
A
N
T
E
L
H
E
I
G
H
T
TOP OF
FIREPLACE
2”
4”
6”
8”
8” MANTEL
2”
4”
6”
5.3 MINIMUM MANTEL CLEARANCES
!
WARNING
RISK OF FIRE, MAINTAIN ALL SPECIFIED AIR SPACE CLEARANCES TO COMBUSTIBLES. FAILURE
TO COMPLY WITH THESE INSTRUCTIONS MAY CAUSE A FIRE OR CAUSE THE APPLIANCE TO
OVERHEAT. ENSURE ALL CLEARANCES (I.E. BACK, SIDE, TOP, VENT, MANTEL, FRONT, ETC.) ARE
CLEARLY MAINTAINED.
WHEN USING PAINT OR LACQUER TO FINISH THE MANTEL, THE PAINT OR LACQUER MUST BE
HEAT RESISTANT TO PREVENT DISCOLOURATION.
73.1