33

W415-1004 / B / 08.10.12

5.1 MINIMUM CLEARANCE TO COMBUSTIBLES

* HORIZONTAL VENT SECTIONS

- A minimum clearance of 1" at the bottom and sides and 2" at the top of the

vent pipe in all horizontal runs to combustibles is required except for clearances in appliance enclosures, see

"MINIMUM ENCLOSURE CLEARANCES" section. Use fi restop spacer W010-1777 (supplied).

* VERTICAL VENT SECTIONS

- A minimum of 1" all around the vent pipe on all vertical runs to combustibles is

required. Use fi restop spacer W500-0096 (not supplied).

Minimum clearance to combustible construction from appliance and vent surfaces:

Combustible Framing:

-

0" to stand-offs

-

1" to bottom and sides of the vent pipe*

-

2" to top of the vent pipe*

Combustible Finishing:

-

0" to rear

-

0" to front face top and sides

-

13" recessed depth

Rear Vent:

-

39 1/8" to enclosure top from base of the unit

-

45 1/8" to ceiling from base of the unit

Top Vent:

-

53 1/8" to enclosure top from base of the unit

-

53 1/8" to ceiling from base of the unit

DO NOT BUILD INTO THIS AREA - IT MUST BE LEFT CLEAR TO PROVIDE ADEQUATE CLEARANCE

FOR THE VENT. IN THIS 14” WIDE AREA CENTRED ALONG THE FRONT OF THE APPLIANCE, NO

COMBUSTIBLES ARE ALLOWED.

!

WARNING

13

1

/

4

14”

MINIMUM

1

1

/

2

MAXIMUM

*KEEP FACING MATERIAL 1/4” FROM SIDE OF UNIT
TO ACHIEVE OPENING WIDTH OF 20

1

/

4

”.

NOTE: MUST BE MAINTAINED FOR THE FACING KIT
TO COVER THE OPENING.

* 1

/

4

1

1

/

2

MAXIMUM

*FINISHING

MATERIAL

OPENING

HEIGHT

MUST BE

34

1

/

8

CEMENT BOARD -

REQUIRED FOR

CONTEMPORARY

FRONT ONLY

(CFS19/CFK19)

NON-COMBUSTIBLE

MATERIAL