5- Electrical Installation.
Please conform to all local and national electrical codes for wiring. The heater should be supplied by
a separate cable, of appropriate gauge and with appropriate protection.
Use wires suited for 75ºC. Please refer to the following table Fig. 1.
Fresh Air and Zone Heaters
Recommended wire gauge and protection
Min.
Models
Collar
Wire
Air Flow
THERMO-AIR
THERMO-ZONE
SIZE
Dia. KW Volts Amps. Gauge
Fuses
CFM
TER-6-1120
&
ZON-6-1120
A
6
1
120/1
8.3
12
15
30
TER-6-1208
&
ZON-6-1208
A
6
1
208/1
4.8
12
15
30
TER-6-1240
&
ZON-6-1240
A
6
1
240/1
4.2
12
15
30
TER-6-2120
&
ZON-6-2120
A
6
2
120/1
16.7
12
20
60
TER-6-2208
&
ZON-6-2208
A
6
2
208/1
9.6
12
15
60
TER-6-2240
&
ZON-6-2240
A
6
2
240/1
8.3
12
15
60
TER-8-3208
&
ZON-8-3208
B
8
3
208/1
14.4
12
20
90
TER-8-3240
&
ZON-8-3240
B
8
3
240/1
12.5
12
15
90
TER-8-4208
&
ZON-8-4208
B
8
4
208/1
19.2
10
30
120
TER-8-4240
&
ZON-8-4240
B
8
4
240/1
16.7
12
20
120
TER-8-5208
&
ZON-8-5208
B
8
5
208/1
24.0
10
30
150
TER-8-5240
&
ZON-8-5240
B
8
5
240/1
20.8
10
30
150
TER-8-6240
&
ZON-8-6240
B
8
6
240/1
25.0
10
40
180
TER-10-3208
&
ZON-10-3208
B
10
3
208/1
14.4
12
20
90
TER-10-3240
&
ZON-10-3240
B
10
3
240/1
12.5
12
15
90
TER-10-4208
&
ZON-10-4208
B
10
4
208/1
19.2
10
30
120
TER-10-4240
&
ZON-10-4240
B
10
4
240/1
16.7
12
20
120
TER-10-5208
&
ZON-10-5208
B
10
5
208/1
24.0
10
30
150
TER-10-5240
&
ZON-10-5240
B
10
5
240/1
20.8
10
30
150
TER-10-6240
&
ZON-10-6240
B
10
6
240/1
25.0
10
40
180
TER-10-8240
N/A
C
10
8
240/1
33.3
8
50
240
TER-10-10240
N/A
C
10
10
240/1
41.6
6
60
300
TER-10-12240
N/A
C
10
11.5 240/1
47.9
6
60
345
TER-12-6240
N/A
C
12
6
240/1
25.0
10
40
180
TER-12-8240
N/A
C
12
8
240/1
33.3
8
50
240
TER-12-10240
N/A
C
12
10
240/1
41.6
6
60
300
TER-12-12240
N/A
C
12
11.5 240/1
47.9
6
60
345
To convert Cubic Feet per Minute to liters per second,
multiply the CFM value by 0.47
A
B
C
X
Y
Z
DIMENSIONS IN INCHES
SIZE X
Y
Z
A
11.5 8.0
11.5
B
11.5 10.0 13.5
C
15.5 12.0 15.5