Check Installation

• Complete the Pre-startup Checklist found in the

Integrated Technologic IOM.

• Perform pre-start procedures outlined in the pump

IOM.

Apply Power

WARNING. The pump may start if a start

signal is present on DI18.

• Unlock and turn on disconnects and breakers to

apply power.

Configure Parameters

• The controller is programmed with 4 different set-ups

that configure the controller for 4 different

applications.

Set-up 1 Constant pressure control with wired pressure

transducer. Setpoint = 15 psi. Transducer connected to

AI53. AI53 is configured for a 40 psi pressure transducer.

Set-up 2 Flow control with wired flow transducer.

Setpoint = 150 GPM. Transducer connected to analog

input AI53. AI53 is configured for a 300 GPM flow

transducer.
Set-up 3 Sensorless pressure control. The controller setpoint is

preconfigured at the factory based on the order request.

Set-up 4 Sensorless flow control. The controller setpoint is

preconfigured at the factory based on the order request.

NOTE: Set-up 3 is the default set-up.

• Select the application set-up

by setting parameter 0-10 to

match the application as

follows:

• Press

• Select 0-** by pressing

• Select 0-1* and press

• Press to edit 0-10 Active

Set-up

• Select the desired Set-up us-

ing the arrow keys and

press to save the change.

• Press to return to the

status screen

• Use My Personal Menu to

configure the application

parameters.

• Press

• Press to select My Personal Menu

• Set the parameters in My Personal Menu based on

the application requirements.

Collect System Data

• Controller Part #

• Controller Serial #

• Motor Part #

• Pump Part #

• Input Voltage

• Nominal Motor Current

• Nominal Motor Speed

• Nominal Motor Power