• Ensure input power connections are properly

torqued.

• Route control wiring to the drive. Use shielded cable

for control wiring.

• Do not run control wiring in the same conduit as

power wiring.

• Connect the control wires by using a flat blade

screwdriver to open the spring terminal as shown.

• Hold the spring terminal open and insert the control

wire. Release the screwdriver to close the spring

terminal and secure the connection.

REQUIRED CONNECTION: The factory default set-

tings for the controller require a start signal on DI18.

NOTE: If using a transducer for feedback, set the

analog input configuration switches A53 (AI53)

or A54 (AI54) under the keypad.

U = 0-10V, I = 4-20mA

Relay

Terminal Number

Parameter Number

Default Setting or

Description

Function For Set-up 3

01, 02, 03

5-40 Relay 1

[160] No Alarm

Form C Relay Outputs

04, 05, 06

5-40 Relay 2

[5] Running

12, 13

-

+24V DC

24 V dc used for digital inputs and

external transducers.

18

5-10

[8] Start

Start/Stop

19

5-11

[0] No Operation

Unused digital input

27

5-12

[0] No Operation

Unused digital input

29

5-13

[0] No Operation

Unused digital input

32

5-14

[0] No Operation

Unused digital input

33

5-15

[0] No Operation

Unused digital input

20

-

Common

Common for digital inputs and 24V supply

39

-

AO Common

Common for analog output

42

6-50

4-20mA Motor Freq

Analog output

50

-

+10V

10V DC analog supply voltage. 15mA maximum.

53

6-1*

Not Used

Analog input 53

54

6-2*

Not Used

Analog input 54

55

-

AI Common

Common for analog input

61

-

Shield Connection

RC filter for cable shield

68

8-**

+

RS485 Interface +

69

8-**

-

RS485 Interface -

Digital I/O

Analog I/O

Comm.