• Ensure input power connections are properly
torqued.
• Route control wiring to the drive. Use shielded cable
for control wiring.
• Do not run control wiring in the same conduit as
power wiring.
• Connect the control wires by using a flat blade
screwdriver to open the spring terminal as shown.
• Hold the spring terminal open and insert the control
wire. Release the screwdriver to close the spring
terminal and secure the connection.
REQUIRED CONNECTION: The factory default set-
tings for the controller require a start signal on DI18.
NOTE: If using a transducer for feedback, set the
analog input configuration switches A53 (AI53)
or A54 (AI54) under the keypad.
U = 0-10V, I = 4-20mA
Relay
Terminal Number
Parameter Number
Default Setting or
Description
Function For Set-up 3
01, 02, 03
5-40 Relay 1
[160] No Alarm
Form C Relay Outputs
04, 05, 06
5-40 Relay 2
[5] Running
12, 13
-
+24V DC
24 V dc used for digital inputs and
external transducers.
18
5-10
[8] Start
Start/Stop
19
5-11
[0] No Operation
Unused digital input
27
5-12
[0] No Operation
Unused digital input
29
5-13
[0] No Operation
Unused digital input
32
5-14
[0] No Operation
Unused digital input
33
5-15
[0] No Operation
Unused digital input
20
-
Common
Common for digital inputs and 24V supply
39
-
AO Common
Common for analog output
42
6-50
4-20mA Motor Freq
Analog output
50
-
+10V
10V DC analog supply voltage. 15mA maximum.
53
6-1*
Not Used
Analog input 53
54
6-2*
Not Used
Analog input 54
55
-
AI Common
Common for analog input
61
-
Shield Connection
RC filter for cable shield
68
8-**
+
RS485 Interface +
69
8-**
-
RS485 Interface -
Digital I/O
Analog I/O
Comm.