Powerware 9395 UPS 10001100 kVA Manuel d'utilisation
Page 35

UPS INSTALLATION PLAN AND UNPACKING
EATON Powerware
®
9395 UPS (1000–1100 kVA) Installation and Operation Manual
S 164201764 Rev 1 www.powerware.com
3−15
Table 3-11. Supplied External Wiring Terminal Hardware Kit
Part
Size
Quantity
Terminals Used On
Eaton Part Number
Bolt, Grade 5
M10 x 25 mm
15
Ground
180190078−087
Bolt, Grade 5
M12 x 50 mm
98
Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral
180190078−115
Flat Washer
M10
15
Ground
180500036−100
Flat Washer
M12
196
Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral
180500036−120
Conical Washer
M10
15
Ground
180500037−100
Conical Washer
M12
98
Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral
180500037−120
Nut
M12
98
Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral
180200001−07
Table 3-12. Recommended Installation Parts and Tools (Not Supplied by Eaton
)
Part
Size
Quantity
Manufacturer
Part Number
Notes
Long Barrel 2-Hole Lug
2/0 AWG
As required
Thomas & Betts
54862BE
Copper wire only
3/0 AWG
Thomas & Betts
54864BE
4/0 AWG
Thomas & Betts
54866BE
250 MCM
Thomas & Betts
54868BE
300 MCM
Thomas & Betts
54870BE
350 MCM
Thomas & Betts
54872BE
400 MCM
Thomas & Betts
54874BE
500 MCM
Thomas & Betts
54876BE
Manual Hydraulic Crimp Tool
14 Ton
1
Thomas & Betts
TBM14M
Die Set
N/A
1
Thomas & Betts
15506