Table 3-6, or, Table 3-6 and table 3-7 – Powerware 9395 UPS 10001100 kVA Manuel d'utilisation
Page 31

UPS INSTALLATION PLAN AND UNPACKING
EATON Powerware
®
9395 UPS (1000–1100 kVA) Installation and Operation Manual
S 164201764 Rev 1 www.powerware.com
3−11
Table 3-6. Input/Output Ratings and External Wiring Requirements for the Three UPM Powerware 9395−1100/650, 9395−1100/750, and
9395−1100/825 – Common Battery
Basic Unit Rating
Units
Rating 50/60 Hz
kVA
kW
650
591
750
682
825
750
Input and Output Voltage
Volts
480/480
480/480
480/480
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
A
Amps
891
1028
1130
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(4)
AC Input to UPS Bypass (Four Wire)
Full Load Current
(3) Phases, (1) Ground
B
Amps
782
902
992
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(4)
AC Input to UPS Bypass (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
Amps
782
902
992
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(5)
DC Input from Battery Disconnect to UPS
(1) Positive, (1) Negative
C
Total Amps
1280
1502
1600
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
500
(6)
AC Output to Critical Load (Four Wire)
Full Load Current
(3) Phases, (1) Ground
D
Amps
782
902
992
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(4)
AC Output to Critical Load (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
D
Amps
782
902
992
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(5)
Neutral Bonding Jumper (Four Wire Output Only)
Minimum Conductor Size
Number
–
AWG or kcmil
(each)
4/0
(1)
NOTE Callout letters
A
,
B
,
C
, and
D