Product overview and specifications – Dell Basic PDU Manuel d'utilisation
Page 2

2
Dell Basic Rack Power Distribution Unit—Product Overview and Specifications
Product Overview and Specifications
The Dell Basic Rack PDU distributes power to the devices in the rack.
O
UTLETS
— The Rack PDU has twenty-one (21) IEC-320-C13 outlets and six (6) IEC-320-C19 outlets.
P
OWER
CORD
— The Rack PDU has a 3-m (10-ft) NEMA, 4-pin L15-30P power cord.
WG8H2
Electrical
Input connection
NEMA, 4-pin L15-30P
Acceptable input voltage
208 VAC
±
10%, 3-phase
Maximum input current (phase)
24 A (derated)
Input frequency
50/60 Hz
Input power
8.6 kVA
Output voltage
208 VAC (Line-to-Line)
Output connections
Twenty-one (21) IEC-320-C13;
Six (6) IEC-320-C19
Maximum output current (outlet)
IEC-320-C13: 12 A; IEC-320-C19: 16 A
Maximum output current (bank)
16 A (derated)
Overload protection (internal)
Three (3) 20 A 2-pole hydraulic-magnetic circuit
breakers
Physical
Dimensions
(H x W x D)
162.5 x 5.5 x 4.6 cm
(64.0 x 2.2 x 1.7 in)
Depth at breakers: 9.4 cm (3.7 in)
Shipping dimensions
(H x W x D)
187.5 x 22.6 x 13.5 cm
(73.8 x 8.9 x 5.3 in)
Weight
6.5 kg (14.2 lb)
Shipping weight
8.3 kg (18.2 lb)
Environmental
Maximum elevation
(above MSL)
Operating
Storage
0 to 3048 m (0 to 10,000 ft)
0 to 15 240 m (0 to 50,000 ft)
Temperature
Operating
Storage
0 to 50°C (32 to 122°F)
–15 to 60°C (5 to 140°F)
Humidity
Operating
Storage
5 to 95%, non-condensing
5 to 95%, non-condensing