Warnings – Lenze E82MV752 4Bxxx Manuel d'utilisation
Page 3

3
EDK82MV752-BB DE/EN/FR 1.0
Warnings!
ƒ
Motor Overload Protection
–
For information on the protection level of the internal overload
protection for a motor load, see the corresponding manuals or
software helps.
–
If the integral solid state motor overload protection is not used,
external or remote overload protection must be provided.
ƒ
Branch Circuit Protection
–
The integral solid state protection does not provide branch circuit
protection.
–
Branch circuit protection has to be provided externally in accordance
with corresponding instructions, the National Electrical Code and any
additional codes.
ƒ
If mounted on a motor the environmental rating tests for Type 4 and
Type 12 shall be performed.
ƒ
Fuses/circuit breakers
–
See this manual for maximum fuse/circuit breaker sizes and circuit
breaker types.
–
Voltage rating of the fuses and circuit breakers must at least be
suitable for the input voltage.
ƒ
E82MV251_2B ... E82MV371_2B (0.25 kW ... 0.37 kW, 240 V devices):
–
Suitable for use on a circuit capable of delivering not more than
5000 rms symmetrical amperes, 240 V maximum, when protected by
fuses or circuit breakers.
–
Suitable for use on a circuit capable of delivering not more than
50000 rms symmetrical amperes, 240 V maximum, when protected by
CC, J, T or R class fuses.
–
Maximum surrounding air temperature: 0 ... +60 °C
–
> +40 °C: reduce the rated output current by 2.5 %/°C
–
Use 60/75 °C or 75 °C copper wire only.
ƒ
E82MV551_4B ... E82MV752_4B (0.55 kW ... 7.5 kW, 400/500 V devices):
–
Suitable for use on a circuit capable of delivering not more than
5000 rms symmetrical amperes, 500 V maximum, when protected by
fuses or circuit breakers.
–
Circuit breakers only for use in WYE 480/277V source.
–
Suitable for use on a circuit capable of delivering not more than
50000 rms symmetrical amperes, 500 V maximum, when protected by
CC, J, T or R class fuses.
–
Maximum surrounding air temperature: 0 ... +60 °C
–
> +40 °C: reduce the rated output current by 2.5 %/°C
–
Use 60/75 °C or 75 °C copper wire only.