3.4 MINIMUM AIR TERMINAL LOCATION CLEARANCES

INSTALLATIONS

CANADA

U.S.A.

A

12”

(304.8mm)

12”

(304.8mm)

Clearance above grade, veranda porch, deck or balcony.

B

12”

(304.8mm)

Δ

9” (228.6mm)

Δ

Clearance to windows or doors that open.

C

12”

(304.8mm)*

12”

(304.8mm)*

Clearance to permanently closed windows.

D

18”

(457.2mm)**

18”

(457.2mm)**

Vertical clearance to ventilated soffi ts located above the terminal within a horizontal distance of
2’ (0.6m) from the center line of the terminal.

E

12”

(304.8mm)**

12”

(304.8mm)**

Clearance to unventilated soffi t.

F

0” (0mm)

0” (0mm)

Clearance to an outside corner wall.

G

0” (0mm)

0” (0mm)

Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney,
etc.).

2” (50.8mm)

2” (50.8mm)

Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase,
etc.).

H

3’ (0.9m)

3’ (0.9m)***

Clearance to each side of the center line extended above the meter / regulator assembly to a
maximum vertical distance of 15’ (4.6m).

I

3’ (0.9m)

3’ (0.9m)***

Clearance to a service regulator vent outlet.

J

12”

(304.8mm)

9” (228.6mm)

Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other
appliance.

K

6’ (1.8m)

3’ (0.9m)

Clearance to a mechanical air supply inlet.

L

7’ (2.1m) ‡

7’ (2.1m)***

Clearance above a paved sidewalk or paved driveway located on public property.

M

12”

(304.8mm)††

12”

(304.8mm)***

Clearance under a veranda, porch or deck.

N

12”

(304.8mm)

12”

(304.8mm)

Clearance above the roof.

O

2’ (0.6m) †*

2’ (0.6m) †*

Clearance from an adjacent wall including neighbouring buildings.

P

8’ (2.4m)

8’ (2.4m)

Roof must be non-combustible without openings.

Q

3’ (0.9m)

3’ (0.9m)

See chart for wider wall dimensions.

R

6’ (1.8m)

6’ (1.8m)

See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an
opening between the terminal and the open side of the structure.

S

12”

(304.8mm)

12”

(304.8mm)

Clearance under a covered balcony

Δ

The terminal shall not be located less than 6 feet (1.8m) under a window that opens on a horizontal plane in a structure with three walls and a roof.

*

Recommended to prevent condensation on windows and thermal breakage

**

It is recommended to maximize the distance to vinyl clad soffi ts.

***

This is a recommended distance. For additional requirements check local codes.

A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces..

††

Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the fl oor.

†*

Recommended to prevent recirculation of exhaust products. For additional requirements check local codes.

††*

Permitted only if the balcony is fully open on a minimum of one side.

12.2D

R

Q

S

G

P

COVERED BALCONY APPLICATIONS

††*

Q

MIN

R

MAX

MAX

R

= 3 feet

(0.9m)

= 2 x

”IHHW

(4.6m)

Q

ACTUAL