Owner's MAnuAl |

Installation & Handling

Please read this manual before operating your

ACR-160 Automatic Charge Isolator
Description

The ACR-160 microprocessor controlled battery isolator

is used in starter and auxiliary battery systems like on

boats, RV, service vans. It supervises the starter state

of charge and, therefore, avoids starting problems.

The ACR-160 can also be used as a voltage dependent

switch. The working principle is the following:

- The ACR-160 lets the starter battery be recharged by

the alternator until a voltage of 13.2V (26.4V) during

at least 7 seconds is reached. Then the two batteries

are put in parallel by the contact of the relay.

- The secondary users are normally connected to the

auxiliary battery. The relay opens when the batteries

voltage reaches 12.8V (25.6V) during at least 60 sec-

onds. This way the starter battery remains charged. If

a battery charger is connected to the auxiliary battery

and this battery reaches a voltage of 13.2V (26.4V)

during at least 7 seconds, the relay closes and charges

at the same time the starter battery. This is an ad-

vantage if the vehicle remains stationary over a long

period of time. If the battery charger is disconnected

and the battery voltage reaches 12.8V (25.6V) during

at least 60 seconds, then the ACR-160 separates again

the two batteries.

Start Assistance

The ACR-160 has an additional connection enabling an

assistance to the starting. If the connection STATUS is

connected to the starter contact, the ACR-160 contact

closes and this way the 2 batteries contribute to the

engine start. Caution: When this function is used.

Very high currents may go through the relay contact

by the start of bigger engines. these high currents may

damage the contact of the aCR-160 if they exceed its

nominal current.

Voltage Dependent Switch

In some cases, it is needed to have a powerful DC source

supply but only when the engine is running. The ACR-

160 allows also this kind of installations.
It is sufficient to simply connect "+" of the starter bat-

tery to the connection A1, the system ground to the

connection MINUS and the positive of the equipment to

be supplied to the connection A2. When the engine runs

and a voltage of 13.2V (26.4V) during at least 7 seconds

is reached, the equipment is then powered through the

contact of the ACR-160.

Remote Indication of Relay ON Condition

Connect external LED as shown.

Disable Relay Permanently

Use external switch as shown.

Protection Against Over Voltages

The ACR-160 has also a function enabling to

protect the battery and the appliances that are

connected to it against an over voltage generated,

for instance, by a defective alternator. As soon as a

voltage higher than 16V (32V) is detected, the

contact of the ACR-160 opens immediately.

Installation

To implement the function «start assistance», a fuse

protected connection has to be carried out between the

connection STATUS and the contact of the starter con-

tact. a short-circuit between the positive and negative

of the batteries can damage your system. Make sure

that the connections are properly done!

Technical Specifications

Supply ....................... Automatic detection 12/24V
Max. current .....................................................160A
Peak current .......................... 480A for 250 millisec
Battery connection ............................................ M8
other connections .......................... Faston 6,3 mm
Cable cross section ...................................... 50mmq
Consumption oFF ..........12V=1.8mA / 24V=2.0mA
Consumption oN .........12V=340mA / 24V=170mA
Minimum charge time ........................... 60 seconds
Fast opening: < 11.8V (12V) / 23.6 (24V) after 4 sec
Dimensions: 106.4 x 73 x 57.2 mm / 4.2 x 2.9 x 2.3 in
Weight: 0.46 kg. / 1.0 lb.

Connections

A1: Positive terminal of the starter battery
A2: Positive terminal of the auxiliary battery

(If the function «voltage dependent switch»

is needed, connect the equipment positive here).
STATUS:

1. Contact to "+", relay is closed (Start assistance)

2. No connection on STATUS , normal operation

3. Contact to "", relay remains open
MINUS: Negative terminal

(Caution - this connection must always

remain connected via a fuse of 1a)
LED: Connection for remote indication

for status of ACR-160)

+

+12VDC (+24VDC)

To the starter contact

(optional, see installation)

STARTER

BATTERY

1A

+

ALTERNATOR

200A

1A

1A

AWG

#16

A1

A2

LED

STATUS

MINUS

+

AUXILIARY

BATTERY

200A

1A

+ –

EXTERNAL

CHARGER

External LED

to indicate

activation

of relay

External

switch to

disable

the relay

permanently

CAUTION!

Wire sizes to be based on

maximum current and 2%

voltage drop.
Fuses to match wire sizes.

AWG

#16

AWG

#16

AWG

#16

ACR-160

2 | SAMLEX AMERICA INC.