Quick start guide ram 9000 series – Red Lion RA 9000 Cellular RTU Manuel d'utilisation
Page 2

Red Lion Controls
• 20 Willow Springs Circle • York, PA 17406 • USA • +1 717 767 6511
www.redlion.net
QUICK START GUIDE
RAM 9000 Series
LTE, HSPA & EVDO
VERIFY CELLULAR CONNECTIVITY
Confirm the following on the GUI (see Figure B) after logging into
the unit:
Activation:
“Succeeded” or “Unavailable”
Connection:
“Enabled”
IP Address: Populated with a network IP address
Signal Strength has GREEN bars populated. If you see any RED
bars represented under the Signal Strength graphics, please
consult the User Manual. Ethernet (Eth0) should show “Up” and
show the network issued IP address.
NOTE:
If “Unavailable” and connection “Unknown” browse to the
StatusEZ Config Wizard or Network Tab Cellular
Connection Configuration and input the APN field. EVDO
models will automatically try to activate on a periodic basis.
If you were unable to confirm this status on the Main page, please
refer to the RAM 9000 Software Guide for troubleshooting steps
at
For more information to set up Modbus features, please refer to
the RAM 9000 User Guide available a
If you are able to confirm this status, then your unit is
successfully connected to the cellular network.
RED LION WIRELESS TECHNICAL SUPPORT
If you have followed all of the instructions up to this point, have
verified with your carrier that you are not having an authentication
problem, have verified that you have adequate cellular signal
reception, and your unit is still not communicating, then it is time to
contact Red Lion Wireless Technical Support at
[email protected] or 1-877-432-9908 and we will be happy to
assist you in getting your unit operational.
HARDWARE STATUS LEDs
LED
State
Description
P1/P2
ON
Power is applied to the associated input
OFF
Power is not being applied to the associated input
GPS
ON
Position fix available
OFF
No position fix available
RESET
ON
Unit is booting. Not Ready
OFF
Unit is functioning normally
WAN
ON
Cellular connection is established
OFF
Cellular Connection is not established
STATUS
ON
Unit is booting up.
OFF
Normal operation
FLASH
Unit entering reflashing mode. Do not disturb.
STROBE
System erros Contact Red Lion support.
*See the RAM 9000 Series Hardware & Installation Guide for more
information on LEDs.
INSTALLATION AND HAZARDOUS AREA WARNINGS
All power, input and output (I/O) wiring must be in accordance with Class
I, Division 2 wiring methods and in accordance with the authority having
jurisdiction.
Suitable for use in Class I, Division 2, Groups A, B, C and D hazardous
locations, or non-hazardous locations only.
WARNING
– EXPLOSION HAZARD – SUBSTITUTION OF COMPONENTS
MAY IMPAIR SUITABILITY FOR CLASS 1, DIVISION 2.
WARNING
– EXPLOSION HAZARD – WHEN IN HAZARDOUS
LOCATIONS, DISCONNECT POWER BEFORE REPLACING OR WIRING
MODULES.
WARNING
– EXPLOSION HAZARD – DO NOT DISCONNECT EQUIPMENT
UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN
TO BE NONHAZARDOUS.
WARNING
– EXPLOSION HAZARD – BATTERIES MUST ONLY BE
CHANGED IN AN AREA KNOWN TO BE NON-HAZARDOUS.
These products are operator interface units to be used within control
panels. These devices are intended for use in Class I, Division 2,
Hazardous Locations, industrial control applications. The enclosure shall
be suitable for the location.
A minimum IP54 rated enclosure is needed for ATEX unless an
equivalent degree of protection is supplied by the location.
These products are to be used within control panels in hazardous
locations. The enclosure shall be suitable for this location. Hot-swapping
is not for use in hazardous locations.
AVERTISSEMENTS POUR INSTALLATION ET ENDROITS
DANGEREUX
Tout courant, câblage entrée et sortie (I / O) doit être conforme aux
méthodes de câblage à la Classe I, Division 2 et conformément à
l'autorité compétente.
Cet appareil est adapté pour utilisation en Classe I, Division 2, Groupes
A, B, C, D endroits dangereux ou endroits non-dangereux.
AVERTISSEMENT
– RISQUE D’EXPLOSION – LA SUBSTITUTION DE
TOUT COMPOSANT PEUT NUIRE À LA CONFORMITÉ DE CLASSE I,
DIVISION 2
AVERTISSEMENT
– RISQUE D’EXPLOSION – LORSQUE DANS DES
ENDROITS DANGEREUX, DÉBRANCHEZ LE CORDON D'ALIMENTATION
AVANT DE REMPLACER OU DE BRANCHER LES MODULES.
AVERTISSEMENT
– RISQUE D’EXPLOSION – NE DÉBRANCHEZ PAS
L'ÉQUIPEMENT À MOINS QUE L'ALIMENTATION AIT ÉTÉ COUPÉE OU
QUE L’ENVIRONNEMENT EST CONNU POUR ÊTRE NON DANGEREUX.
WARNING
– RISQUE D’EXPLOSION - LES BATTERIES DOIVENT ÊTRE
REMPLACÉES DANS UNE ZONE CONNUE COMME ÉTANT NON-
DANGEREUSE.
Ces produits sont des unités d'interface opérateur qui doivent être
utilisés à l'intérieur des panneaux de commande. Ces appareils sont
destinés à une utilisation en Classe I, Division 2, zones dangereuses,
applications de contrôle industriel. L'enclos doit être adapté à
l’environnement lieu.
Un boîtier IP54 minimum est nécessaire pour ATEX à moins qu’un degré
équivalent de protection est fourni par l'emplacement.
Lorsque dans des endroits dangereux, ces produits doivent être utilisés
dans des panneaux de contrôle. Pas de remplacement à chaud des
modules dans les zones dangereuses.